Goodrive300 Series VFD    Function parameters 
49 
Detailed instruction of parameters 
state. The starting frequency is not limited in the 
lower limit frequency. 
Output frequency 
fmax
t1
T
f1 set by P01.01
f1
t1 set by P01.02
The braking 
current before 
starting 
The VFD will carry out DC braking at the braking 
current  set  before  starting  and  it  will  speed  up 
after the DC braking time. If the DC braking time 
is set to 0, the DC braking is invalid.   
The stronger  the  braking current, the bigger the 
braking  power.  The  DC  braking  current  before 
starting  means  the  percentage  of  the  rated 
current of the VFD. 
Setting range of P01.03: 0.0–100.0% 
Setting range of P01.04: 0.00–50.00s 
The braking 
time before 
starting 
The  changing  mode  of  the  frequency  during 
start-up and running. 
0: Linear type 
The  output  frequency  increases  or  decreases 
linearly. 
fmax
 
Output frequency
t1 t2
T
0:  Decelerate  to  stop:  after  the  stop  command 
becomes valid, the VFD decelerates to decrease 
the  output  frequency  during  the set  time. When 
the  frequency  decreases  to  P01.15,  the  VFD 
stops.