Goodrive300 Series VFD    Function parameters 
99 
Detailed instruction of parameters 
The function is applied to the proportional gain P 
of PID input. 
P  determines  the  strength  of  the  whole  PID 
adjuster. The parameter of 100 means that when 
the  offset  of  PID  feedback  and  given  value  is 
100%, the adjusting range of PID adjustor is the 
Max. frequency (ignoring integral and differential 
function). 
Setting range: 0.00–100.00 
This  parameter  determines  the  speed  of  PID 
adjustor  to  carry  out  integral  adjustment  on  the 
deviation of PID feedback and reference.   
When  the  deviation  of  PID  feedback  and 
reference  is  100%,  the  integral  adjustor  works 
continuously  after  the  time  (ignoring  the 
proportional  effect  and  differential  effect)  to 
achieve the Max. Frequency (P00.03) or the Max. 
Voltage  (P04.31).  Shorter  the  integral  time, 
stronger is the adjustment.   
Setting range: 0.00–10.00s 
This  parameter  determines  the  strength  of  th  e 
change  ratio  when  PID  adjustor  carries  out 
integral  adjustment  on  the  deviation  of  PID 
feedback and reference.   
If  the  PID  feedback  changes  100%  during  the 
time, the adjustment of integral adjustor (ignoring 
the  proportional  effect  and  differential  effect)  is 
the Max. Frequency (P00.03) or the Max. Voltage 
(P04.31). Longer the integral time, stronger is the 
adjusting.   
Setting range: 0.00–10.00s 
This parameter means the sampling cycle of the 
feedback.  The  adjustor  operates  each  sampling 
cycle. The longer the sapling cycle is, the slower 
the response is.