Goodrive300 Series VFD Function parameters
108
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
LED tens:
0: The VFD continues to work after underload
pre-alarm
1: The VFD continues to work after underload
pre-alarm and the VFD stops to run after overload
fault
2: The VFD continues to work after overload
pre-alarm and the VFD stops to run after
underload fault
LED hundreds :
0: Detection all the time
1: Detection in constant running
Setting range of P11.09: P11.11200%
Setting range of P11.10: 0.13600.0s
P11.11
Underload
pre-alarm
detection
If the VFD current or the output current is lower
than P11.11, and its lasting time is beyond
P11.12, the VFD will output underload pre-alarm.
Setting range of P11.11: 0P11.09
Setting range of P11.12: 0.13600.0s
50%
P11.12
Underload
pre-alarm
detection time
1.0s
P11.13
Output
terminal action
during fault
Select the action of fault output terminals on
undervoltage and fault reset.
0x000x11
LED ones:
0: Action under fault undervoltage
1: No action under fault undervoltage
LED tens:
0: Action during the automatic reset
1: No action during the automatic reset
0x00
P11.14
Speed
deviation
detection
0.050.0%
Set the speed deviation detection time.
10.0%
P11.15
Speed
deviation
detection time
This parameter is used to see the speed deviation
detection time.
0.5s