Goodrive300 Series VFD Function parameters
85
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
BIT15: reserved
P07.08
Frequency
coefficient
0.0110.00
Displayed frequency=running frequency × P07.08
1.00
P07.09
Rotation
speed
coefficient
0.1999.9%
Mechanical rotation speed =120 × displayed
running frequency × P07.09/motor pole pairs
100.0%
P07.10
Linear speed
coefficient
0.1999.9%
Linear speed= Mechanical rotation speed ×
P07.10
1.0%
P07.11
Rectifier
bridge module
temperature
-20.0120.0°C
P07.12
Inverter
module
temperature
-20.0120.0°C
P07.13
Software
version
1.00655.35
P07.14
Local
accumulative
running time
065535h
P07.15
High bit of
power
consumption
Display the power used by the VFD.
The power consumption of the VFD
=P07.15×1000+P07.16
Setting range of P07.15: 065535kWh (×1000)
Setting range of P07.16: 0.0999.9kWh
P07.16
Low bit of power
consumption
P07.17
Reserved
Reserved
P07.18
The rated
power of the
VFD
0.43000.0kW
P07.19
The rated
voltage of the
VFD
501200V
P07.20
The rated
current of the
VFD
0.16000.0A
P07.21
Factory bar
code 1
0x00000xFFFF

Table of Contents