Goodrive300 Series VFD Function parameters
87
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P07.30
Previous 3
fault type
27: Parameter uploading fault (UPE)
28: Parameter downloading fault (DNE)
29: PROFIBUS communication fault (E-DP)
30: Ethernet communication fault (E-NET)
31: CANopen communication fault (E-CAN)
32: Grounding short circuit fault 1 (ETH1)
33: Grounding short circuit fault 2 (ETH2)
34: Speed deviation fault (dEu)
35: Maladjustment (STo)
36: Undervoltage fault (LL)
P07.31
Previous 4
fault type
P07.32
Previous 5
fault type
P07.33
Running
frequency at
current fault
0.00Hz
P07.34
Ramp
reference
frequency at
current fault
0.00Hz
P07.35
Output voltage
at current fault
0V
P07.36
Output current
at current fault
0.0A
P07.37
Bus voltage at
current fault
0.0V
P07.38
The Max.
temperature at
current fault
0.0°C
P07.39
Input terminals
state at
current fault
0
P07.40
Output
terminals state
at current fault
0
P07.41
Running
frequency at
last fault
0.00Hz
P07.42
Ramp
reference
0.00Hz

Table of Contents