Goodrive300 Series VFD Function parameters
92
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
pulse occurs.
The value of P08.26 cannot be greater than that
of P08.25.
The function is illustrated as below:
HDI
Y, HDO,
RO1, RO2
The set
count value
is reached.
The
specified
count value
is reached.
Setting range of P08.25: P08.2665535
Setting range of P08.26: 0P08.25
P08.27
Set running
time
Pre-set running time of the VFD. When the
accumulative running time achieves the set time,
the multi-function digital output terminals will
output the signal of "running time arrival".
Setting range: 065535m
0m
P08.28
Automatic
fault reset
times
Automatic fault reset times: set the automatic
fault reset times. If the reset time exceeds this set
value, the VFD will stop to wait maintenance.
Interval time of automatic fault reset: the interval
between the time when the fault occurs and the
time when the reset action occurs.
Setting range of P08.28: 010
Setting range of P08.29: 0.13600.0s
0
P08.29
Interval time of
automatic fault
reset
1.0s
P08.30
Frequency
decreasing
ratio of the
dropping
control
The output frequency of the VFD changes as the
load. And it is mainly used to balance the power
when several VFDs drive one load.
Setting range: 0.0050.00Hz
0.00Hz
P08.31
Motor shifting
Goodrive300 supports the shift between two
motors. This function is used to select the shifting
channel.
LED ones: shifting channel
0: terminal shifting; digital terminal is 35
1: Modbus communication shifting
2: PROFIBUS/CANopen communication shifting
3: Ethernet communication shifting
4: Reserved
LED tens: shifting enabling in operation
0