Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-72-
Detailed instruction of parameters
59: Brake feedback signal
60: Joystick zero position signal
61: Hierarchical reference terminal 1
62: Hierarchical reference terminal 2
63: Hierarchical reference terminal 3
64: Hierarchical reference terminal 4
65: Hierarchical reference terminal 5
Polarity
selection of
input
terminals
The function code is used to set the polarity of input
terminals.
Set the bit to 0, the input terminal is anode.
Set the bit to 1, the input terminal is cathode.
The setting range: 0x000~0x1FF
Set the sampling filter time of S1~S8 and HDI
terminals. If the interference is strong, increase the
parameter to avoid the disoperation.
The setting range: 0.000~1.000s
Virtual
terminals
setting
Enable the input function of virtual terminals at the
communication mode.
0: Virtual terminals are invalid
1: Modbus communication virtual terminals are valid
2~4: Reserved
Terminals
control
running
mode
Set the operation mode of the terminals control
0: 2-wire control 1; the enabling and the direction
combine into one. This mode is widely used. It
determines the rotation direction by the defined FWD
and REV terminals command.