Goodrive35 Series Closed-loop Vector Control VFD Function parameters
115
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modif
y
P15 Group PROFIBUS/CANopen function
P15.00
Module type
0: PROFIBUS;
1: CANopen
Select communication protocol
0
P15.01
Module address
0127
This function code is used to designate the address
of the VFD.
Note: 0 is the broadcast address, when set it as
broadcast address, only receive the radio command
of the upper monitor other than answering the upper
monitor.
2
P15.02
PZD2 receiving
0: Invalid
1: Setting frequency (0Fmax (unit: 0.01 Hz))
2: PID reference, range (01000, 1000 corresponds
to 100.0%)
3: PID feedback, range (01000, 1000 corresponds
to 100.0%)
4: Torque setting (-30003000, 1000 corresponds to
100.0% the rated current of the motor)
5: Upper frequency of forward rotation
(0Fmax unit: 0.01 Hz))
6: Upper frequency of reverse rotation (0Fmax
(unit: 0.01 Hz))
7: Electromotion torque upper limit (03000, 1000
corresponds to 100.0% of the rated current of the
motor)
8: Brake torque upper limit (02000, 1000
corresponds to 100.0% of the rated current of the
motor)
9: Virtual input terminals command
Range: 0x0000x1FF
10: Virtual output terminals command
Range: 0x000x0F
11: Voltage setting value (special for V/F separation)
(01000,1000 corresponds to 100.0% the rated
voltage of the motor)
12: AO output set value 1 (-1000+1000, 1000
corresponds to 100.0%)
0
P15.03
PZD3 receiving
0
P15.04
PZD4 receiving
0
P15.05
PZD5 receiving
0
P15.06
PZD6 receiving
0
P15.07
PZD7 receiving
0
P15.08
PZD8 receiving
0
P15.09
PZD9 receiving
0
P15.10
PZD10 receiving
0
P15.11
PZD11 receiving
0
P15.12
PZD12 receiving
0