Goodrive35 Series Closed-loop Vector Control VFD Basic operation instruction
168
Function
code
Name
Detailed instruction of parameters
Default
value
P06.14
AO1 output
0: Running frequency
1: Set frequency
2: Ramps reference frequency
3: Running speed
4: Output current (relative to 2 times the rated
current of the VFD)
5: Output current (relative to 2 times the rated
current of the motor)
6: Output voltage (relative to 1.5 times the
rated voltage of the VFD)
7: Output power (relative to 2 times the rated
power of the motor)
8: Set torque value (relative to 2 times the
rated torque of the motor)
9: Output torque (relative to 2 times the rated
torque of the motor)
10: Analog AI1 input value
11: Analog AI2 input value
12: Analog AI3 input value
13: Input value of high-speed pulse HDIA
14: Set value 1 of Modbus communication
15: Set value 2 of Modbus communication
16: Set value 1 of PROFIBUS\CANopen
communication
17: Set value 2 of PROFIBUS\CANopen
communication
18: Set value 1 of Ethernet communication
19: Set value 2 of Ethernet communication
2021: Reserved
22: Torque current (bipolar, 100%
corresponds to 10 V)
23: Excitation current (100% corresponds to
10 V)
24: Setting frequency (bipolar)
25: Ramp reference frequency (bipolar)
26: Operation speed (bipolar)
27: Reserved
0
P06.15
AO2 output
0
P06.16
HDO high-speed pulse
output
0
P06.17
Lower output limit of AO1
-300.0%P06.19