Goodrive35 Series Closed-loop Vector Control VFD Function parameters
62
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modif
y
speed compensation characteristic mentioned here
means reducing the threshold of the overload
protection of the motor whose running frequency is
below 30 Hz.
2: Variable frequency motor (without low speed
compensation) Because the heat-releasing effect of
the specific motors won’t be impacted by the rotation
speed, it is not necessary to adjust the protection
value during low-speed running.
P02.27
Motor 1 overload
protection
coefficient
Motor overload multiple M = Iout/(In × K)
In is the rated current of the motor, Iout is the output
current of the VFD and K is the motor overload
protection coefficient.
The smaller K is, the greater M is, and the more
likely protection is implemented.
When M=116%, protection is performed after motor
overload lasts for 1 hour; when M=150%, protection
is performed after motor overload lasts for 12
minutes; when M=180%, protection is performed
after motor overload lasts for 5 minutes; when
M=200%, protection is performed after motor
overload lasts for 60 seconds; and when M 400%,
protection is performed immediately.
1
5
12
60
116%
200%
Time (min)
Motor overload
multiple
150% 180%
Setting range: 20.0%120.0%
100.0%
P02.28
Motor 1 power
display correction
coefficient
This function code is used to adjust the power
display value of motor 1 only.
Setting range: 0.003.00
1.00
P02.29
Parameter display of
motor 1
0: Display according to the motor type
1: Display all
0