Goodrive100-PV Series Solar Pumping VFD Function parameters
26
Detailed illustration of parameters
autotuning when high control accuracy is
needed.
2: Static autotuning
It is suitable in the cases when the motor
cannot de-couple form the load. The
autotuning for the motor parameter will
impact the control accuracy.
3: Static autotuning 2 (No autotuning for
non-load current and mutual inductance)
Function
restore parameter
0: No operation
1: Restore the default value
2: Clear fault records
Note:
The function code will restore to 0 after
finishing the operation of the selected
function code.
Restoring to the default value will cancel
the user password. Use this function with
caution.
P01 Group Start-up and stop control
0: Decelerate to stop. After the stop
command becomes valid, the VFD
decelerates to reduce the output
frequency during the set time. When the
frequency decreases to 0Hz, the VFD
stops.
1: Coast to stop. After the stop command
becomes valid, the VFD ceases the output