Goodrive100-PV Series Solar Pumping VFD Function parameters
25
Function
code
Name
Detailed illustration of parameters
Default
Modify
selection
runs in the forward direction. FWD/REV
indicator is off.
1: Runs at the opposite direction. The
VFD runs in the reverse direction.
FWD/REV indicator is on.
Modify the function code to shift the
rotation direction of the motor. This effect
equals to the shifting the rotation direction
by adjusting either two of the motor lines
(U, V and W). The motor rotation direction
can be changed by QUICK/JOG on the
keypad. Refer to parameter P07.02.
Note:
When the function parameter comes back
to the default value, the motor’s running
direction will come back to the factory
default state, too.
In pump application scenarios, the VFD
cannot run in the reverse direction. This
function code cannot be modified.
2: Forbid to run in reverse direction: It can
be used in some special cases if the
reverse running is disabled.
P00.15
Motor parameter
autotuning
0: No operation
1: Rotation autotuning
Comprehensive motor parameter
autotune.
It is recommended to use rotation
0