Doc. CEI12166 Rev. 1 Pag. 17 Of 47
. With the first selection, the recording is continuous, including the delay between tests. This selection
is not to be used unless for short tests: the long delay reduces screen resolution and time measurement
accuracy.
. With the second selection, the recording is performed at the highest resolution, around the Open or
Close commands: this is to be selected in case of long sequences.
2.3.5.4 Recording options
This selection defines how test results will be recorded: pressing it, the following window is displayed.
The timing definition can be displayed pressing “HELP diagram: the following window is displayed.
As you see from timing definitions, it is possible to superimpose a Close command to the Open
command: this is obtained setting the “Open to close delay “ smaller than the “Open coil duration”.
The “Pre-trigger” duration applies only to the beginning of the test (or sequence).
The “Recording duration” includes all delays: it must be bigger than “Pre-trigger” + “OC delay” + “CO
delay” + the CB timings, so that no significant part of the test is lost. On the other side, it should not be
too big, as it defines the test result dimension, hence the number of test results that can be kept in
memory. Pressing HELP diagram, the following window explains the definition of terms.