13
IMPORTANT:
• Cooling capacity is measured at an ambient temperature of DB 95°F, WB 83°F.
• Noise level is measured at a distance of 3.28" (1m) away from the front of the portable air conditioner, while it is
in cooling mode.
• Power consumption is measured when the fan is running at the highest speed setting.
• These specifications are for reference only. For the actual data on your unit, please refer to the rating label on the
back of your portable air conditioner.
• If the operating environment is higher than the max operating temperature (88°F (31.1°C)), or lower than the
minimum operating temperature (61°F (16.1°C)), the unit may not work as intended.
SELF-DIAGNOSIS CODES
SPECIFICATIONS
SKU
IVAPAC12BTU
IVAPAC14BTU
Cooling Capacity
12000 BTU/hr 14000 BTU/hr
Dehumidification
3.16 pts/day 3.16 pts/day
Cooling Power Usage
1385 W/12.2 A 1535 W/12.5 A
Air Flow
206 CFM 206 CFM
Power Source
115 V/60 Hz 115 V/60 Hz
Noise Level
55 dB(A) 55 dB(A)
Product Weight
65 lbs. (29.5 kg) 66.1 lbs. (30 kg)
Operating Temp.
61°F – 88°F (16.1°C – 31.1°C) 61°F – 88°F (16.1°C – 31.1°C)
Product Dimensions
17.5
″
W x 28.75
″
H x 14.5
″
D
(44.45 x 73.03 x 36.83 cm)
17.5
″
W x 28.75
″
H x 14.5
″
D
(44.45 x 73.03 x 36.83 cm)
Refrigerant
R-410A R-410A
Error Code
Potential Cause
Possible Solution
E1
Outside Pipe Temperature Sensor
Failure
Turn the unit o and back on again to remove the
error code. If the code appears again, contact
Ivation® Customer Care.
E2
Inside Temperature Sensor
Failure
Turn the unit o and back on again to remove the
error code. If the code appears again, contact
Ivation® Customer Care.
E3/E4 Coil Pipe Sensor Failure Contact Ivation® Customer Care.
E7 Low-Temperature Protection
Make sure the room temperature is above 41°F (5°C)
during operation. If the code appears again, contact
Ivation® Customer Care.
E8
Overheating Protection Turn the unit o and check the surrounding room
temperature. If the code continues to appear, contact
Ivation® Customer Care.