Optima 1400-1700
Dimensions, clearance and plumbing connections
Required installation space for the heat pump.
Minimum distance from the pump to the wall is 300 mm.
Minimum distance in front of the pump 1000 mm, to the sides 500 mm.
If a roof is installed it must be positioned at least 1.5 m above the heat
pump to avoid the recirculation of cold air.
705
920
1660
From above
Right-hand sideBack
1 Heat transfer uid out external G25
2 Heat transfer uid in external G25
3 Drainage external G25
Right
Left
Front
1
2
3