6
This manual gives you all the information necessary to install the heat
pump. The guide is divided into several parts in the order in which installa-
tion and commissioning must be carried out.
Before starting the installation:
The heat pump may be temporarily tilted with the compressor
downwards. It must never be laid down or transported horizontally.
Check that plumbing connections in the heat pump are intact and have
not shaken loose during transport.
If the heat pump is used in a system with fan-assisted radiators, the
water volume in the system is very small. During defrosting, the heat
pump draws some of the energy from the heating system, cooling
it down. It is therefore important that the fans in the fan-assisted
radiators run during defrosting, alternatively are connected to a tank of
approximately 100 litres.
Wiring should be kept as short as possible to protect the system from
downtime, for example during a thunderstorm.
Before the commissioning the heating system must be filled up and
completely vented.
Important information for the installer
Checklist
The following checklist will give you a general description of how the installation
should be carried out.
1. Position the heat pump on a solid base.
2. Install the incoming and outgoing pipes for the heat pump.
3. Install the drainage pipe for the heat pump.
4. Install the new hot water heater, hot water sensor and three-way valve if used.
5. Install G2 heat carrier pump.
6. Install a mixing valve if not already installed.
7. Fit the particle filter.
8. Connect the heat pump to the heating system.
9. Install the control cabinet and the accessory unit for electric/oil-fired boiler.
10. Install the flow sensor, outdoor sensor, and room sensor if used.
11. Connect the CANbus wiring between the heat pump and the control cabinet.
12. Connect the heating installation to the power supply via a safety switch and
any earth fault breaker.
13. Fill and vent the heating system before commissioning.
14. Commission the heating installation by making all the necessary settings on
the control panel.
15. Check the heating installation after commissioning.
Warning
For reasons of safety the main power
supply must be disconnected before
working on the heat pump.
!
Note
Only qualifi ed installers may carry
out the installation. The installer must
follow applicable rules and regula-
tions and recommendations from the
supplier.
Important information to the installer / Checklist