Commissioning report
Vent 402 – 6721815546 (2021/03)
44
Customer address: First name, last name:
Address:
City:
Telephone:
Installation company: Name:
Street address:
City:
Telephone:
Product information: Product model:
TTNR:
Serial number:
FD No.:
Installation components: Receipt/value
Room controller Yes | No
Buffer cylinder Yes | No
Type.volume (litres)
Other components Yes | No
Which components?
Minimum spacing heat pump
Heat pump is placed on a firm, even surface Yes | No
Connections to heat pump
Have the connections been done in a professional way? Yes | No
Who laid/delivered the power cable?
Heating:
Pressure in expansion vessel set at .......bar Yes | No
Heating system flushed before installation Yes | No
Particulate filter cleaned Yes | No
Minimum permissible flow through heating system set Yes | No
Electrical connection:
Low voltage lines are installed with a minimum distance of 100 mm
from 230 V/400 V lines
Yes | No
Output limiter connected Yes | No
Both diodes on output limiter lit Yes | No
Outdoor temperature sensor (T1) correctly positioned on the coldest
side of the house
Yes | No
Power supply connection:
Phase sequence L1 L2 L3, N and PE in heat pump correct Yes | No
Power supply connected according to installation instructions Yes | No
Securing of heat pump and auxiliary heater, tripping properties Yes |
No
Manual mode:
Function test of individual component groups (pump, mixing valve, 3-
way valve, compressor etc.)
Yes | No
Notes:
The temperature values in the menu are checked/documented Yes | No
T0 ______ °C
T1 ______ °C
TW1 ______ °C
TC0 ______ °C