ENTERING THE SETUP MENU
Press twice and hold the SETUP key
until the word DAMPER appears on the
LCD. (Figure 2)
SETTING THE MINIMUM DAMPER
POSITION
Press the SETUP key again and the
LCD will display the minimum damper
position. The factory default is 10%
which means the damper is driven 90%
closed after a heating or cooling call is
satisfied. Press the UP and DOWN keys
to change the minimum damper
position. Position may be adjusted in
10% increments. (Figure 3)
SETTING THE MAXIMUM DAMPER
POSITION
Press the SETUP key again and the
LCD will display the maximum damper
position for heating and cooling. The
factory default is 100% which means the
damper can drive fully open with a call
for heating or cooling. Position may be
adjusted in 10% increments using the
UP and DOWN keys. (Figure 4)
SETTING A UNIT NUMBER
Press the SETUP key again and the
LCD will display the word UNIT. The
factory default is 00. This number can
be used to assign the Z-2000-T to a
particular HVAC unit. Use the UP and
DOWN keys to assign a UNIT number
from 00 to 99. (Figure 5)
FIGURE 2
FIGURE 3
FIGURE 4
www.jacksonsystems.com
1.888.652.9663
6
FIGURE 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Jackson Systems COMFORT SYSTEM Z-2000-T and is the answer not in the manual?

Jackson Systems COMFORT SYSTEM Z-2000-T Specifications

General IconGeneral
BrandJackson Systems
ModelCOMFORT SYSTEM Z-2000-T
CategoryThermostat
LanguageEnglish

Related product manuals