J-200 Series
10.7  Air Controls
Certain jet systems have their own air control. Each control  
introduces air into the water lines that supply that specic 
jet group. Simply turn the air control of choice 
counterclockwise to open or clockwise to close. To 
minimize heat loss, all air controls should be closed when the spa is not 
in use.
11.0  Automatic Filtration Cycles
The control system activates a programmable “standard” or “economy” 
ltration cycle to remove debris from your spa. These cycles use the low 
speed jets pump 1 and lter cartridge to quickly clear “skim” the water 
of debris and minimize their “bathtub ring” affect while the spa is in use 
or during a programmed lter cycle. Models equipped with the optional 
24-hour circulation pump offer the added benet of 24-hour ltration for 
pennies a day!
Apart from their ltration benet, each ltration mode also effects the 
operation of the spa heater. Refer to sections 11.1 and 11.2 for details.
 Without 
Circulation Pump Option (All Models)
Standard ltration/heating modes (F1-F3) are typically selected by 
customers in cold climates where heat up times are extended due 
to lower ambient temperatures. In either of these modes, the water 
temperature is regulated by the set temperature, low-speed jets pump 
1 and heater which turns on as needed. After the programmed set 
temperature is reached, the heater and low speed pump turn off, only to 
turn back on during a heat call or during the next programmed ltration/
heating cycle.
 With 
Standard ltration/heating modes (F0-F3) are typically selected by 
customers in cold climates where heat up times are extended due 
to lower ambient temperatures. In either of these modes, the water 
temperature is regulated by the set temperature, 24-hour circulation 
pump and heater which turns on as needed. After the programmed set 
temperature is reached, the heater turns off and the circulation pump 
continues to operate 24-hours to lter and clean your spa.
28