Table 3. Pool or Spa Only Controls
Table 4. Dual Equipment Controls
DIP Switch # OFF ON
1
Aux. 1 = Any equipment Aux. 1 = Pool cleaner
2
Aux. 2 = Any equipment Aux. 2 = Low speed for a two speed lter pump.
Filter pump circuit becomes high speed.
3
Aux. 3 = Any equipment Aux. 3 = Spa spillover effect. Combo controls
only.
4
Heater cool down operates. Heater cool down disabled.
5
Normal operation Factory adjustment. When this switch is on, tem-
perature delays are eliminated and solar tempera-
ture is displayed. Do not leave this switch in the
ON position.
6
Spare No change.
7
Spare No change.
8
After thermostat setting has been reached, the
heater will remain off for three (3) minutes.
After thermostat setting has been reached, the
heater will remain off for ve (5) minutes.
DIP Switch # OFF ON
1
Aux. 1 = Any equipment Aux. 1 = Pool cleaner
2
Aux. 2 = Any equipment Aux. 2 = Low speed for a two speed lter pump.
Filter pump circuit becomes high speed.
3
Spare No change.
4
Heater cool down operates. Heater cool down disabled.
5
Normal operation Factory adjustment. When this switch is on, tem-
perature delays are eliminated and solar tempera-
ture is displayed. Do not leave this switch in the
ON position.
6
Separate pool and spa heaters Sharing one heater
7
No solar system installed. Air temperature
displayed.
Changes air sensor to solar sensor. Air tempera-
ture no longer displayed. AquaLink RS Adjust-
able Freeze Kit must be added fro freeze protec-
tion.
8
After thermostat setting has been reached, the
heater will remain off for three (3) minutes.
After thermostat setting has been reached, the
heater will remain off for ve (5) minutes.