CONFIGURATION AND CALIBRATION – Software Calib.
Page 67 of 80
you will be able to click on the OK button which will bring you back to the
initial Rudder Feedback Calibration window with the new values indicated
on the right side of the screen.
Click the SET button before closing in order to accept the new values and
to enter them to the DSC.
SCP Meter Calibration Window
If any rudder indicators are
connected to the SCPs, an
adjustment will be required to
ensure that the indicators display
the correct rudder angle and
command. From the drop down
list first select the CENTER
option. All indicators connected
to the SCPs should now read
exactly midships. If this is not
the case make the appropriate
adjustment to the indicator offset at each indicator. Next select PORT
from the drop down list. All indicators should now read some angle to
port. If this is not the case then the indicator signal polarity must be
reversed at each indicator that is not displaying a port angle. With PORT
selected from the drop down list each set of indicators connected to the
SCP’s for Rudder Angle, Digital Helm Rudder Order and/or FFU Input 1
Rudder Order may require a gain adjustment to ensure that each indicator
displays the correct hard over angle.
Doc No.: MAN01504, 20-02-06 DSC 100 & MCP 100 Manual