ELECTRIC
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
When fuses are used they must be dual element, time delay, current limiting, class RK1 or
RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or National
Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For others, calculate/verify
correct breaker size according to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
OVEN
kW
APPROX. AMP DRAW
CIRCUIT
BREAKER
60 Hz 50 Hz
208 2 24 123
175
220 2 20 98
125
230 2 22 97
125
240 2 24 107 108 150
208 2 30 152
200
220 2 26 125 127 175
230 2 28 123 130 175
240 2 30 132 133 175
220 2 20
100 150
230 2 22
104 150
208 3ø 3 24 74
100
220 3ø 3 20 60 61 80
230 3ø 3 22 56 63 80
240 3 24 65 66 90
208 3ø 3 30 91
125
220 3ø 3 30 86
125
220 3ø 3 26 76 77 100
230 3ø 3 28 71 78 100
240 3 30 79
100
416 4 30 49 50 70
380 3ø 4 20
39 50
400 4 22
40 60
416 4 24
41 60
240 3 30
80 125
380 3ø 4 26
48 70
400 4 28
48 70
208 3ø 3 24 71
90
220 3ø 3 20 57 57 80
240 3 24 63 63 80
380 3ø 3 20 33
50
440 3 20 29
40
460 3 22 30
40
480 3 24 32
50
208 3ø 3 30 88
125
220 3ø 3 26 73 73 100
240 3 30 77 78 100
380 3ø 3 26 42
60
440 3 26 37
50
460 3 28 38
50
480 3 30 39
50
230 3ø 3 22
60 80
380 3ø 4 or 3 20
33 50
400 4 or 3 22
35 50
416 4 or 3 24
36 50
230 3ø 3 28
75 100
380 3ø 4 or 3 26
43 60
380 3ø 4 or 3 30
49 70
400 4 or 3 28
44 60
416 4 or 3 30
45 60
440 4 or 3 26
37 50
b. Electric Models Only
ALL electrically heated dryers must be connected to the electric service shown on the dryers data
label. The connecting wires must be properly sized to handle the rated current.
Check your local code for breaker and wire size 5/19/15