ClgOcc-Sp AV 29608 R/W ClgOcc-Sp
OCC Cooling
Setpoint
The occupied cooling setpoint
(45.0–98.0°F)
ClgUnocc-Sp AV 29609 R/W ClgUnocc-Sp
UNOCC Cooling
Setpoint
The unoccupied cooling setpoint
(46.0–99.0°F)
OprClg-Sp AV 29610 R OprClg-Sp
Operating Cooling
Setpoint
Displays the active operating cooling
setpoint (0.0–100.0°F)
C1A-RunTime AV 29627 R C1A-RunTime
Compressor
Accumulated
Runtime 1A
Displays the operating hours of
compressor 1A (hours)
C1B-RunTime AV 29628 R C1B-RunTime
Compressor
Accumulated
Runtime 1B
Displays the operating hours of
compressor 1B (hours)
C2A-RunTime AV 29630 R C2A-RunTime
Compressor
Accumulated
Runtime 2A
Displays the operating hours of
compressor 2A (hours)
C1AOnTimer AV 29631 R C1AOnTimer
Min. ON Time
Remaining 1A
Displays the minimum time
remaining for compressor 1A to turn
off (seconds)
C1BOnTimer AV 29632 R C1BOnTimer
Min. ON Time
Remaining 1B
Displays the minimum time
remaining for compressor 1B to turn
off (seconds)
C2AOnTimer AV 29634 R C2AOnTimer
Min. ON Time
Remaining 2A
Displays the minimum time
remaining for compressor 2A to turn
off (seconds)
C1A-ASCDTmr AV 29635 R C1A-ASCDTmr
Anti-Short Cycle
Delay Time
Remaining 1A
Displays the time remaining for
compressor 1A to turn on (seconds)
C1B-ASCDTmr AV 29636 R C1B-ASCDTmr
Anti-Short Cycle
Delay Time
Remaining 1B
Displays the time remaining for
compressor 1B to turn on (seconds)
C2A-ASCDTmr AV 29638 R C2A-ASCDTmr
Anti-Short Cycle
Delay Time
Remaining 2A
Displays the time remaining for
compressor 2A to turn on (seconds)
SLP-1 AV 29671 R SLP-1
Suction Line
Pressure 1
Displays the active system 1 suction
line pressure (psi)
SLP-2 AV 29672 R SLP-2
Suction Line
Pressure 2
Displays the active system 2 suction
line pressure (psi)
LLP-1 AV 29675 R LLP-1
Liquid Line
Pressure 1
Displays the active system 1 liquid
line pressure (psi)
LLP-2 AV 29676 R LLP-2
Liquid Line
Pressure 2
Displays the active system 2 liquid
line pressure (psi)
SLT-1 AV 29679 R SLT-1
Suction Line
Temperature 1
Displays the active system 1 suction
line temperature (°F)
SLT-2 AV 29680 R SLT-2
Suction Line
Temperature 2
Displays the active system 2 suction
line temperature (°F)
LLT-1 AV 29683 R LLT-1
Liquid Line
Temperature 1
Displays the active system 1 liquid
line temperature (°F)
LLT-2 AV 29684 R LLT-2
Liquid Line
Temperature 2
Displays the active system 2 liquid
line temperature (°F)
Table 32: BACnet Points List (Continued)