48 Johnson Controls Ducted Systems
Table 18: Airflow performance - bottom duct application
J06ZH (6.5 ton) bottom duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied drive Standard 1.5 HP and drive High static 2 HP and drive
1800 775 0.31 850 0.53 924 0.72 998 0.89 1072 1.05 1147 1.20 1224 1.35 1303 1.5113841.6914691.89
2000 803 0.45 878 0.67 952 0.86 1026 1.03 1100 1.19 1175 1.34 1252 1.49 1331 1.6514121.8314972.03
2200 838 0.60 913 0.82 986 1.01 1060 1.19 1134 1.34 1210 1.49 1286 1.65 1365 1.8114471.9815322.18
2400 878 0.78 953 1.00 1027 1.19 1100 1.36 1174 1.52 1250 1.67 1327 1.82 1405 1.98 1487 2.16 - -
2600 923 0.98 997 1.20 1071 1.39 1145 1.56 1219 1.72 1294 1.87 1371 2.02 1450 2.18----
2800 971 1.20 1046 1.42 1119 1.61 1193 1.78 1267 1.94 1343 2.09 1419 2.24 - - - - --
3000 1023 1.44 1097 1.66 1171 1.85 1245 2.03 1319 2.18 - - - - - -----
320010771.7111511.9312252.1212992.29------------
340011331.9912082.21----------------
2 HP and field supplied drive
J07ZH (7.5 ton) bottom duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied drive Standard 1.5 HP and drive High static 3 HP and drive
2000 803 0.45 878 0.67 952 0.86 1026 1.03 1100 1.19 1175 1.34 1252 1.49 1331 1.6514121.8314972.03
2200 838 0.60 913 0.82 986 1.01 1060 1.19 1134 1.34 1210 1.49 1286 1.65 1365 1.8114471.9815322.18
2400 878 0.78 953 1.00 1027 1.19 1100 1.36 1174 1.52 1250 1.67 1327 1.82 1405 1.9814872.1615722.36
2600 923 0.98 997 1.20 1071 1.39 1145 1.56 1219 1.72 1294 1.87 1371 2.02 1450 2.1815322.3616172.56
2800 971 1.20 1046 1.42 1119 1.61 1193 1.78 1267 1.94 1343 2.09 1419 2.24 1498 2.40 1580 2.58 1665 2.78
3000 1023 1.44 1097 1.66 1171 1.85 1245 2.03 1319 2.18 1394 2.33 1471 2.49 15502.6516322.8217173.02
3200 1077 1.71 1151 1.93 1225 2.12 1299 2.29 1373 2.45 1448 2.60 1525 2.75 16042.9116863.0917713.29
3400 1133 1.99 1208 2.21 1282 2.41 1356 2.58 1430 2.73 1505 2.88 1582 3.04 16613.2017423.37 - -
3600 1192 2.30 1267 2.52 1341 2.71 1414 2.88 1489 3.04 1564 3.19 1641 3.34 - - - ---
3800 1253 2.63 1327 2.85 1401 3.04 1475 3.21 1549 3.37 - - - - - -----
3 HP and field supplied drive
J08ZH (8.5 ton) bottom duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field supplied drive
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS
4
Standard 2 HP and drive High static 3 HP and drive
2600 674 0.71 731 0.88 786 1.05 838 1.24 887 1.42 933 1.59 974 1.74 1010 1.87 1040 1.97 1064 2.03
2800 689 0.86 746 1.02 801 1.20 854 1.38 903 1.56 948 1.73 989 1.88 1025 2.01 1056 2.11 1080 2.17
3000 707 1.01 764 1.17 819 1.35 872 1.53 921 1.71 966 1.88 1007 2.03 1043 2.16 10742.2610982.32
3200 728 1.17 785 1.33 840 1.51 892 1.69 941 1.87 987 2.04 1028 2.20 1064 2.33 10942.4211182.48
3400 751 1.34 808 1.51 863 1.68 915 1.87 964 2.05 1010 2.22 1051 2.37 1087 2.50 11172.6011412.66
3600 776 1.53 833 1.70 888 1.87 941 2.06 990 2.24 1035 2.41 1076 2.56 1112 2.69 11422.7911672.85
3800 804 1.74 861 1.90 916 2.08 969 2.26 1018 2.44 1063 2.61 1104 2.77 1140 2.90 1170 2.99 - -
4000 835 1.97 892 2.13 947 2.31 999 2.49 1048 2.67 1094 2.84 1135 2.99 - -----
4200 867 2.21 924 2.37 979 2.55 1032 2.73 1081 2.91 1127 3.08 - - - -----
3 HP and field supplied drive

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls J ZH Series and is the answer not in the manual?

Johnson Controls J ZH Series Specifications

General IconGeneral
BrandJohnson Controls
ModelJ ZH Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals