CKM-CE75-E1M Hardware Information
24-10707-112 Rev. D
2-8
DC Output at 12V
Setting
Voltage: 11.3 - 12.0 V
Max Current: 4.5 A
Ripple: 120 mV
Regulation: ±2%
Efficiency: 85% (120 VAC, 85% (120 VAC, 60 Hz In, Full Load, No
Batt)
DC Output at 24V
Setting
Voltage: 23.5 - 24.0 V
Max. Current: 3 A
Ripple: 120 mV
Regulation: ±2%
Efficiency: 85% (120 VAC 60Hz In, full load, no battery)
Battery Size and Type: 4–40 Ah Sealed Lead Acid or Gel Cell
Charge Current: 1 A (±10%) Max.
Fuse Ratings DC1: ATM 7.5 A
DC2: ATM 7.5 A
Battery: ATM 7.5 A
Terminal block: 5A, Slow-Blo, 5x20mm
BTU Output 33
Fault
Setpoints Low AC: 95 V (±6%)
Earth GND: 2000 ohms
Output Voltage: ±10% of nominal
Battery Voltage ±10% of nominal
Battery presence:
6–15 V (12 V Setting),
11–29 V (24 V Setting)
Fault Relay Contacts AC FLT:
1 A
at 24 VDC, 0.6 power factor
SYS FLT:
1 A
at 24 VDC, 0.6 power factor
Environmental
Specifications
Ambient Temperature: 32 to 120°F (0 to 49°C)
Ambient Humidity: 93% at 32°C (90°F) maximum
Storage Temperature: -22 to 158°F (-30 to 70°C)
CKM-FPO75
Mechanical
Specifications
Size (L x W x H):
6 in. x 4 in. x 2 in. (15.2 cm x 10.2 cm x 5.1 cm)
Appx. weight: 0.75 lbs. (0.340 kg)
Specification Value