CKM-CE75-E1M Installation and Wiring
24-10707-112 Rev. D
3-5
Use the following connectors and crimp tool to terminate the standby battery
wiring.
B
ATTERY WIRING
The following optional configuration is not allowed for UL 294 and UL 1076
installations.
The optional battery backup feature uses one PowerSonic, Model PS-1270,
12 VDC, 7 Ah, sealed lead acid battery per power supply.
The RED (+) and BLK (-) cables are provided with the enclosure. Wire the
battery as shown.
Figure 3-5: Battery Wiring
When connecting the battery:
• Observe polarity.
• Make sure battery terminals do not contact the enclosure during installation
or during use.
Description Manufacturer Part Number Crimp Tool
#10 ring terminal, 16-14 AWG to be
used at battery terminal. Two ring
terminals are required.
TE Connectivity/
Amp
2-34161-2 58433-3
0.250 series, Ultra-Fast, fully
insulated Faston tab terminal,16-14
AWG to be used to connect battery
to BDM. Two Faston tabs are
required.
TE Connectivity/
Amp
3-520107-2 58628-1
CKM-CE75-E1M
Battery
RED
BLK
CKM-FPO75
Note: Not all
components of the
CKM-CE75-E1M
are shown.
Components are
not to scale.
BAT
+ BAT
+