CKM-CE75-E1M Installation and Wiring
24-10707-112 Rev. D
3-4
CONNECTING TO STANDBY POWER
For additional standby power wiring information, refer to the manufacturer’s
documentation for Listed model EB-80 battery enclosure.
For UL 294 and UL 1076 installations, the CKM-CE75-E1M is intended to be
used with model EB-80 battery box and one 12VDC, 40Ah sealed lead acid
battery for standby power.
Figure 3-4: Connecting to Standby Power
Use Listed 14AWG stranded wire to connect the battery to the
CKM-CE75-E1M power supply.
Battery BDM
CKM-FPO75
Power Supply
Positive (+) terminal Red wire
Negative (-) terminal Black wire
BAT+ BAT+
BAT- BAT-
Orange wire DC1+
EB-80
CKM-CE75-E1M
RED
BLK
CKM-FPO75
Note: Not all components are shown. Components are
not to scale. Refer to the Battery Disconnect Module
installation instructions for connection information.
+
Battery
Battery
Disconnect
Module (BDM)
To
BDM
To
Batteries