CKM-CE75-E1M Operations and Maintenance
24-10707-112 Rev. D
5-2
9. If the Earth Ground jumper is enabled, connect a wire from the
ground stud on the enclosure to the DC1+ terminal. The GND FLT
and SYS FLT LEDs should light. Remove the wire and the GND
FLT and SYS FLT LEDs should extinguish. Repeat for the DC1
terminal.
10. When a standby battery set is used, remove AC power from the
CKM-FPO power supply. Verify that the DC1 LED remains lit and
that the AC FLT LED lights. Reconnect AC power and verify that the
AC FLT extinguishes.
M
AINTENANCE PROCEDURES
The following are the maintenance instructions for the CKM-FPO75 power
supply system.
Disconnect AC power prior to servicing.
Verify that no fault conditions display on any of the yellow fault LEDs.
Verify the integrity of all fuses and replace as necessary using the fuse
ratings listed in Specifications on page 2-7.
The battery set (if used) should be checked and replaced if found to be
defective or if more than 4 years old (or as required by local code).
Verify that all output voltages are within the range listed in Specifications
on page 2-7.