810754-UTG-C-0214
Johnson Controls Unitary Products 9
COP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input
during the same period.
Furnaces that are listed individually in the above table, such as the RGF1L*P, RGF19*P, and RGF1L*E use Coil Only Ratings.
— = Not Applicable.
HEATING CAPACITY - With High Efficiency Motor Furnaces
MODEL
FURNACE
MODEL
COIL
1
MODEL
HEATING
2
47F17F HSPF
MBH COP KW MBH COP KW STD
14.5 SEER HP WITH HIGH EFFICIENCY MOTOR FURNACES
3
RHP14J184S21
RGF19*AE10 FC/MC/PC32A 18.0 3.78 1.40 11.0 2.50 1.29 8.50
RGF19*AE10 FC/MC/PC37A 18.0 3.66 1.47 11.2 2.44 1.34 7.75
RHP14J244S21
RGF19*AE10 FC/MC/PC32A 22.6 3.46 1.91 14.0 2.30 1.78 7.75
RGF19*AE10 FC/MC/PC37A 22.6 3.54 1.87 14.0 2.36 1.74 7.75
RGF19*BE12 FC/MC/PC35B 22.4 3.52 1.86 13.9 2.34 1.74 7.75
RGF19*BE12 FC/MC/PC43B 22.4 3.60 1.82 13.8 2.40 1.68 8.20
RGF19*CE16 FC/MC/PC35C 22.6 3.46 1.91 14.0 2.32 1.77 7.75
RGF19*CE16 FC/MC/PC43C 22.6 3.54 1.87 14.0 2.36 1.74 7.75
RGF19*CE20 FC/MC/PC35C 22.4 3.58 1.83 13.8 2.38 1.70 8.05
RGF19*CE20 FC/MC/PC43C 22.4 3.66 1.79 13.8 2.42 1.67 8.05
RHP14J304S21
RGF19*BE12 FC/MC/PC43B 30.0 3.92 2.26 34.6 5.16 1.96 9.00
RGF19*CE16 FC/MC/PC43C 30.0 3.90 2.27 34.8 5.16 1.98 9.00
RHP14J364S21
RGF19*BE12 FC/MC/PC43B 34.6 3.66 2.77 19.4 2.56 2.22 7.75
RGF19*CE16 FC/MC/PC43C 34.4 3.72 2.71 19.2 2.62 2.15 7.75
RGF19*CE16 FC/MC/PC48C 34.4 3.66 2.75 20.4 2.72 2.20 8.20
RGF19*CE16 FC/PC60C 34.2 3.66 2.74 20.2 2.70 2.19 8.20
RGF19*CE16 UC48C 34.6 3.70 2.74 20.6 2.74 2.20 8.20
RGF19*CE16 UC60C 34.0 3.62 2.75 18.8 2.52 2.19 8.50
RGF19*CE20 FC/MC/PC43C 34.4 3.74 2.69 19.2 2.62 2.15 7.75
RGF19*CE20 FC/MC/PC48C 34.4 3.68 2.74 20.4 2.72 2.20 8.20
RGF19*CE20 FC/PC60C 34.2 3.66 2.74 20.2 2.72 2.18 8.20
RGF19*CE20 UC48C 34.6 3.72 2.73 20.6 2.74 2.20 8.20
RGF19*CE20 UC60C 34.0 3.62 2.75 18.8 2.52 2.19 8.20
RGF19*DE20 FC/MC/PC48D 34.2 3.70 2.71 20.2 2.74 2.16 8.20
RGF19*DE20 FC/MC/PC60D 34.2 3.68 2.72 20.2 2.72 2.18 8.20
RGF19*DE20 UC48D 34.4 3.74 2.69 20.4 2.78 2.15 8.20
RGF19*DE20 UC60D 34.0 3.64 2.74 18.8 2.54 2.17 8.20
RHP14J424S21
RGF19*CE16 FC/MC62D 40.0 3.58 3.27 26.2 2.54 3.02 7.70
RGF19*CE16 FC/PC60C 40.5 3.52 3.37 26.4 2.46 3.14 7.75
RGF19*CE20 FC/MC62D 39.5 3.70 3.13 25.8 2.60 2.91 7.75
RGF19*DE20 FC/MC/PC60D 40.0 3.64 3.22 25.8 2.54 2.98 8.50
RGF19*DE20 FC/MC62D 39.5 3.70 3.13 25.8 2.62 2.89 7.75
RGF19*DE20 UC60D 39.0 3.48 3.28 25.4 2.44 3.05 7.75
RHP14J484S21
RGF19*CE16 FC/MC62D 48.0 3.66 3.88 31.4 2.54 3.62 8.50
RGF19*CE16 FC/PC60C 48.0 3.24 4.39 29.8 2.26 3.86 7.75
RGF19*CE16 FC64D 48.0 3.72 3.94 31.4 2.58 3.57 8.50
RGF19*CE20 FC/MC62D 48.0 3.74 3.76 31.0 2.60 3.49 8.50
RGF19*CE20 FC64D 48.0 3.82 3.80 31.0 2.66 3.41 9.00
RGF19*DE20 FC/MC/PC60D 48.0 3.34 4.21 29.4 2.32 3.71 8.05
RGF19*DE20 FC/MC62D 48.0 3.76 3.74 31.0 2.60 3.49 9.00
RGF19*DE20 FC64D 48.03.843.7831.02.663.419.00
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Heating MBH based on AHRI standards of 70 °F DB (Dry Bulb) entering indoor air, 72% RH (Relative Humidity) outdoor air with 25 feet of interconnecting piping
and no supplemental electric heat operation.
3. High Efficiency Motor Furnaces have B.O.D (Blower on Delay) standard.