R (5) BI 89 ALARM_5_ON n/a n/a n/a Alarm Buffer #5 (0=Alarm has cleared,
1=Alarm is still active)
R / W (5) BV 90 DF_SW_INST n/a n/a n/a Dirty Filter Switch Installed
R / W (5) BV 93 OCC_COMS_ENA n/a n/a n/a Occupied Thermostat or
Communication Input Enabled
R / W (5) BV 96 VAV_UNOCC_HEAT n/a n/a n/a VAV Unoccupied Heating Enabled
R / W (5) BV 97 THERMO_CONTROL n/a n/a n/a Thermostat Only Control Enable
R / W (5) BV 98 DIFF_ENTH_MODE n/a n/a n/a Differential enthalpy mode enabled
R / W (5) BV 99 COMM_RH n/a n/a n/a Accept Comm Value for RH
R / W (5) BV 100 COMM_OH n/a n/a n/a Accept Comm Value for OH
R / W (5) BV 101 COMM_OAT n/a n/a n/a Accept Comm Value for OAT
R (5) BI 102 4_STG_EXP_PRES n/a n/a n/a Four Stage Expansion board Present
R (5) BI 103 VAV_INTELLI_2_PRES n/a n/a n/a VAV / Intelli-Comfort 2 Expansion
Board Present
R (5) BI 104 FREEZE_STAT_1 n/a n/a n/a Freeze Stat # 1
R (5) BI 105 FREEZE_STAT_2 n/a n/a n/a Freeze Stat # 2
R (5) BI 106 FREEZE_STAT_3 n/a n/a n/a Freeze Stat # 3
R (5) BI 107 FREEZE_STAT_4 n/a n/a n/a Freeze Stat # 4
R / W (5) BV 108 COMM_ST n/a n/a n/a Accept Comm Value for Space
Temperature
R / W (5) BV 109 COMM_IAQ n/a n/a n/a Accept Comm Value for Indoor Quality
Sensor
R / W (5) BV 110 MIN_AMB_SEN n/a n/a n/a Minimum Outdoor Air Sensor Enabled
R / W (5) BV 111 REM_CONT_BAS_ECO
N
n/a n/a n/a Remote Control Third Party BAS
Economizer Enable
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description