1031990-UAD-A-0313
Johnson Controls Unitary Products 19
R (5) BI 71 I_IFAN_STAT n/a n/a n/a Intelli-Comfort Indoor Fan Output
Status (0=output is OFF, 1=output is
ON)
R (5) BI 72 I_FAN_OVER n/a n/a n/a Intelli-Comfort Fan Overload Switch
Input Status (0=open,1=closed)
R (5) BI 73 I_COMP1_STAT n/a n/a n/a Intelli-Comfort Compressor #1 Input
Status (0=output is OFF, 1=output is
ON)
R (5) BI 74 I_LPS1 n/a n/a n/a Intelli-Comfort Low Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open / fault)
R (5) BI 75 I_HPS1 n/a n/a n/a Intelli-Comfort High Pressure Switch
for Compressor #1 Input Status
(1=closed, 0=open / fault)
R (5) BI 76 I_COMP2_STAT n/a n/a n/a Intelli-Comfort Compressor #2 Input
Status (0=output is OFF, 1=output is
ON)
R (5) BI 77 I_LPS2 n/a n/a n/a Intelli-Comfort Low Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open / fault)
R (5) BI 78 I_HPS2 n/a n/a n/a Intelli-Comfort High Pressure Switch
for Compressor #2 Input Status
(1=closed, 0=open / fault)
R (5) BI 79 I_CFAN_STAT n/a n/a n/a Intelli-Comfort Condenser Fan #1 Input
Status (0=output is OFF, 1=output is
ON)
R (5) BI 80 I_GAS_VLVE1 n/a n/a n/a Intelli-Comfort Gas Valve #1 Input
Status
R (5) BI 81 I_LIMIT_1 n/a n/a n/a Intelli-Comfort Limit Switch #1 Input
Status
R (5) BI 82 I_FREEZE_1 n/a n/a n/a Intelli-Comfort Freeze Thermostat
Switch #1 Input Status
(0=open,1=closed)
R (5) BI 83 I_FREEZE_2 n/a n/a n/a Intelli-Comfort Freeze Thermostat
Switch #2 Input Status
(0=open,1=closed)
R (5) BI 85 ALARM_1_ON n/a n/a n/a Alarm Buffer #1 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BI 86 ALARM_2_ON n/a n/a n/a Alarm Buffer #2 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BI 87 ALARM_3_ON n/a n/a n/a Alarm Buffer #3 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BI 88 ALARM_4_ON n/a n/a n/a Alarm Buffer #4 (0=Alarm has cleared,
1=Alarm is still active)
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description