TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 21
SeqOpera Determines the sequence of
operation.
Default: 1
(0): Cooling Only (Off-Cool). The default is Cool.
(1): Heating Only (Off-Heat). The default is Heat.
(2): Cooling and Reheat (Off-Auto-Heat-Cool). The default is Heat.
(3): Heating and Reheat (Off-Heat). The default is Heat.
(4*): Cool/Heat Four-Pipe (Off-Auto-Heat-Cool). The default is Heat.
(5*): Cool/Heat Four-Pipe and Reheat (Off-Auto-Heat-Cool). The
default is Heat.
* Selection option (4.0) for Out1Conf only. (See Out1Conf parameter
earlier in this table.)
Note: Choose the selection option (0): Cooling Only when using a
changeover sensor to allow changeover to occur between
Cooling Only and Heating Only. Choose the selection
option (2): Cooling and Reheat when using a changeover
sensor to allow changeover to occur between Cooling and
Reheat and Heating and Reheat.
Unocc HT Sets the Unoccupied Heating
setpoint value.
Default: 62.0°F/16.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Note: When adjusting the
temperature, press
the UP/DOWN
arrow keys to
change the
temperature in
0.5F°/0.5C°
increments; press
and hold the
UP/DOWN arrow
keys to change the
temperature in
5.0F°/5.0C°
increments.
Unocc CL Sets the Unoccupied Cooling
setpoint value.
Default: 80.0°F/26.5°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Heat max Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Cool min Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Set type Provides the option of temporarily
changing the heating or cooling
setpoint by pressing the UP/DOWN
arrow keys.
Default: permnent
(temporar): Local changes to the heating or cooling setpoints are
temporary, and remain effective for the specified TOccTime.
(permnent): Local changes to the heating or cooling setpoints are
permanently stored in the thermostat memory.
TOccTime Sets the duration of the Temporary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
an Override Function enabled in
the Main User Menu (when the
thermostat is in the Unoccupied
mode)
a temporary heating or cooling
setpoint
Default: 2.0 hrs
Range: 0.0 to 24.0 hrs in 1-hour increments
DoorTime Engages the Unoccupied mode if
the door stays open minimally for
the time specified.
Default: 2.0 min
Range: 1.0 to 10.0 min
Deadband Sets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
Range: 2.0F°/1.0C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C°
increments)
Table 5: Installer Configuration Menu (Part 3 of 4)
Parameter
Appearing
on Display
Description and Default Selection Options

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls TEC2627-2 and is the answer not in the manual?