EasyManua.ls Logo

Johnson Controls TEC3010 - User Manual

Johnson Controls TEC3010
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
TEC3000 Series Wireless Proportional Fan Coil and Individual Zone
Thermostat Controllers with Dehumidification Capability
Installation Instructions
1
Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
The TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers are wireless
networked devices that provide control of the following:
local hydronic reheat valves
pressure-dependent variable air volume (VAV) equipment with or without local reheat
two- or four-pipe fan coils
cabinet unit heaters
other individual zone equipment using a proportional 0 to 10 VDC control input
The networked models are compatible with the WNC1800/ZFR182x Pro Series Wireless Field Bus System that
enables remote monitoring and programming for efficient space temperature control. All models include a USB port
configuration that reduces installation time by allowing simple backup and restore features from a USB drive, which
enables rapid cloning of configuration between like units.
Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to
30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied
times by using additional standby setpoints.
All models feature an intuitive UI with backlit display that makes setup and operation quick and easy. Multiple fan
configurations are supported for fan coil equipment types:
single-speed
multi-speed (two or three discrete speeds)
variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe fan coil units with reheat, and four-pipe fan coil units with or
without reheat. When no heating is required, the thermostat controller monitors space humidity and activates
dehumidification control as necessary. Heat and reheat is used as required to maintain the space temperature. For
optimal dehumidification performance, use a fan coil unit that has a multi-speed or variable-speed fan (VSF).
TEC3000 Series Wireless Proportional Fan Coil and
Individual Zone Thermostat Controllers with
Dehumidification Capability
Installation Instructions
TEC3020-xx-xxx, TEC3021-xx-xxx, TEC3022-xx-xxx, TEC3023-xx-xxx
Part No. 24-10788-19, Rev.
D
Issued July 2018
*241078819D*
24-10788-19, Rev. D
(barcode for factory use only)

Questions and Answers

  • D
    David ShortAug 31, 2025
    What to check if Johnson Controls TEC3010 Controller says Zone Temperature Too Hot?
    • S
      Seth ReedAug 31, 2025
      If your Johnson Controls Controller reports that the zone temperature is too hot, it means the zone temperature has exceeded the configured Zone Temp High Limit. You should verify that the TEC and the RTU cooling are enabled and working properly.
  • L
    lauren94Sep 10, 2025
    What should I do if my Johnson Controls Controller displays Zone Temp Unreliable?
    • T
      Troy OlsonSep 10, 2025
      If your Johnson Controls Controller displays 'Zone Temp Unreliable,' it means all sources of zone temperature, including the onboard sensor, are unreliable. The suggested solution is to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • T
    Tommy JohnsonAug 30, 2025
    Why does my Johnson Controls TEC3010 Controller say 'Cooling Unavailable due to Control Mode' or 'Heating Unavailable due to Control Mode'?
    • M
      Michael AllenAug 30, 2025
      If your Johnson Controls Controller displays 'Idle' with a unit status of 'Cooling Unavailable due to Control Mode' (even when above the cooling setpoint) or 'Heating Unavailable due to Control Mode' (even when below the heating setpoint), it indicates that the control mode setting is incorrect. Here’s what you should do: * If the Control Mode is set to 'Cooling Mode' but the controller is requesting heating, change the Control Mode to 'Auto' or 'Heating'. * If the Control Mode is set to 'Heating Mode' but the controller is requesting cooling, change the Control Mode to 'Auto' or 'Cooling'.
  • K
    kristopher55Sep 12, 2025
    What does Controller Fault mean on Johnson Controls Controller?
    • T
      Theodore ReyesSep 12, 2025
      If your Johnson Controls Controller displays 'Controller Fault', it means the controller has detected an internal fault that it cannot recover from, or an unknown error has prevented the controller from turning on. The suggested solution is to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • A
    Anita WeaverSep 12, 2025
    Why does my Johnson Controls staged equipment shut off prematurely when the PID is running?
    • C
      Cheryl MartinezSep 12, 2025
      If your staged equipment shuts off above the cooling setpoint or below the heating setpoint when the PID is running on the TEC, it is expected behavior. The PID control algorithm minimizes overshoot and energy usage, which may cause the equipment to cycle before reaching the setpoint.
  • J
    Jasmine BishopSep 15, 2025
    What should I do if my Johnson Controls TEC3010 Controller displays Controller Fault?
    • D
      Douglas RoseSep 15, 2025
      If your Johnson Controls Controller displays 'Controller Fault', it means an internal fault was detected and the controller was unable to recover. Order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • L
    Lisa HerreraSep 23, 2025
    What does Supervisory Status = Offline mean on my Johnson Controls TEC3010 Controller?
    • G
      greenjorgeSep 23, 2025
      If your Johnson Controls Controller displays 'Supervisory Status = Offline', it indicates that the supervisory controller isn't communicating with the TEC, the TEC isn't mapped to a JCI Supervisory System, or the WNC Gateway isn't communicating with the TEC. To resolve this: 1. Map the TEC into a JCI Supervisory system. 2. Verify that the PAN’s WNC Gateway is online. 3. Add ZFR Pro Routers/Repeaters into the wireless system.
  • P
    Patricia WebbAug 27, 2025
    Why are OA Lockouts Disabled on my Johnson Controls TEC3010?
    • J
      Joshua NelsonAug 27, 2025
      If OA Lockouts are disabled on your Johnson Controls Controller, it means the local outdoor air temperature sensor has become disconnected or failed, or a network outdoor air temperature sensor has timed out. As a result, the controller is no longer shutting down equipment based on the OA lockout setpoints. Here's what to do: 1. If the outdoor air temperature source was a locally connected sensor, follow the troubleshooting steps for the Outdoor Temp Fail alarm. 2. If the outdoor air temperature source was a BAS, check the BAS to ensure it's online and providing the TEC with temperature readings. If you intentionally removed the BAS mapping, reset sensors through the menu.
  • L
    Larry HannaAug 26, 2025
    Why is the Econ Unavailable on my Johnson Controls TEC3010 Controller?
    • J
      Jeremy McclureAug 26, 2025
      If your Johnson Controls Controller displays 'Econ Unavailable', it means the outdoor air temperature sensor is either not installed, has failed, or has been disconnected, preventing the controller from managing the economizer. To fix this, follow the same steps as for an Outdoor Temp Fail alarm: * Check the wiring of the sensor. * If intentionally disconnected, reset sensors through the menu. * If problems persist, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • F
    Frances BarrettAug 25, 2025
    How do I troubleshoot a Supply Temp Fail error on my Johnson Controls Controller?
    • K
      Kathleen BlackwellAug 26, 2025
      A 'Supply Temp Fail' error on your Johnson Controls Controller means that the external supply temperature sensor is either disconnected or has failed. Here’s how you can troubleshoot it: 1. Check the wiring of the sensor to ensure it is properly connected. 2. If the sensor was intentionally disconnected, reset the sensors through the menu. 3. If the problem continues, order replacement units and return the affected devices to Johnson Controls under the RMA program.

Summary

Applications

North American Emissions Compliance

United States Emissions Compliance

FCC compliance information for digital devices.

Canada Emissions Compliance

Canadian digital apparatus compliance.

Installation Guide

Parts Included in Installation

Lists components included with the thermostat controller.

Location Considerations for Thermostat

Installing the Thermostat Controller

Wiring Procedures

Setup and Adjustments

Overview and Interface

Introduces home screen, icons, and customization options.

USB Port Operations

Firmware updates, backups, and setting restores via USB.

Network and Controller Configuration

Setting up network communication and general controller parameters.

Fan, Mode, and System Settings

Configuring fan types, control modes, zone sizes, and dehumidification.

Occupancy and Scheduling

Managing occupancy sources, schedules, overrides, and setpoints.

Advanced Control Features

Optimal start, PID tuning, binary inputs, aux control, motion sensor.

Commissioning and Diagnostics

Testing, sensor priority, and fault diagnostics.

Menus and Submenus Reference

Troubleshooting Guide

Faults and Solutions

Lists common faults, probable causes, and solutions for troubleshooting.

Repair Information

Guidance on unit replacement and contacting support.

Technical Specifications

Johnson Controls TEC3010 Specifications

General IconGeneral
BrandJohnson Controls
ModelTEC3010
CategoryController
LanguageEnglish

Related product manuals