EasyManua.ls Logo

Johnson Controls TEC3322-1 Series - User Manual

Johnson Controls TEC3322-1 Series
50 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
TEC3000 Series Networked and Wireless Proportional Fan Coil and
Individual Zone Thermostat Controllers with Dehumidification Capability
Installation
Guide
1
Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
The networked TEC3000 Series Thermostat Controllers are stand-alone and field-selectable BACnet® MS/TP or
N2 networked devices. Wireless networked models of the TEC3000 Series Thermostat Controller are also
available. Proportional Fan Coil and Individual Zone Thermostat Controllers provide control of the following:
Local hydronic reheat valves
Pressure-dependent variable air volume (VAV) equipment with or without local reheat
Two- or four-pipe fan coils
Cabinet unit heaters
Other individual zone equipment using an on/off or floating control input
The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/TP or N2
communication capability that enables remote monitoring and programming for efficient space temperature control.
The wireless models are compatible with the WNC1800/ZFR182x Pro Series Wireless Field Bus System that
enables communication with a building automation system (BAS). All models include a USB port configuration that
reduces installation time by allowing simple backup and restore features from a USB drive, which enables rapid
cloning of configuration between like units.
Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to
30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied
times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and operation quick
and easy. For Single-or Two-Stage Economizer Thermostat Controller models, only the single-speed fan
configuration is supported. For TEC3x1x and TEC3x2x models, multiple fan configurations are supported for fan
coil equipment types, as follows:
Single-speed
Multi-speed (two or three discrete speeds)
Variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe fan coil units with reheat, and four-pipe fan coil units with or
without reheat. When no heating is required, the thermostat controller monitors space humidity and activates
dehumidification control as necessary. Heat and/or reheat is used as required to maintain the space temperature.
For optimal dehumidification performance, use a fan coil unit that has a multi-speed or variable-speed fan (VSF).
TEC3000 Series Networked and Wireless Proportional Fan
Coil and Individual Zone Thermostat Controllers with
Dehumidification Capability
Installation Guide
TEC3322-1x-xxx, TEC3323-1x-xxx, TEC3622-1x-xxx, TEC3623-1x-xxx, TEC3022-1x-xxx, TEC3023-1x-xxx
LIT-12013162
Issued May 2019

Questions and Answers

  • J
    john12Aug 27, 2025
    What causes Fan Lock on Johnson Controls Thermostat and how to resolve it?
    • D
      David DickersonAug 27, 2025
      If your Johnson Controls Thermostat displays 'Fan Lock', the switch connected to the BI configured for Fan Lock didn't sense airflow within 10 seconds of starting the fan, and control has been shut down. To resolve this: 1. Inspect equipment to ensure fan functions. 2. Check sensor functionality with an ohmmeter, and verify wiring to the TEC. 3. Reset fault by entering the menu, selecting Fault Status, and selecting the Fan Lock. 4. Order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • T
    Timothy CurrySep 7, 2025
    Why does my Johnson Controls Fan controller display 'Idle' with a 'Heating Unavailable' status due to Control Mode?
    • B
      Brandon MartinezSep 7, 2025
      If your Johnson Controls Fan controller displays 'Idle' with a 'Heating Unavailable' status because of the control mode, it means the control mode is set to Cooling Mode, but the controller is requesting heating. Change the control mode to Auto or Heating.
  • K
    knighttylerAug 27, 2025
    What to do if Johnson Controls Thermostat shows USB Malfunction?
    • V
      Vicki ParkerAug 27, 2025
      If your Johnson Controls Thermostat displays 'USB Malfunction,' it means a USB drive has malfunctioned and drawn more current than allowed. Here's how to troubleshoot: 1. Try inserting and using the USB drive again. 2. Try a new USB drive. 3. If the problem continues, you may need to order replacement units and return the faulty devices to Johnson Controls under the RMA program.
  • T
    Tyler Adams DDSSep 18, 2025
    Why is Heating Ineffective on my Johnson Controls TEC3322-1 Controller?
    • A
      Angela MaySep 18, 2025
      If your Johnson Controls Controller indicates 'Heating Ineffective,' it means the supply air temperature hasn't increased above the configured Supply Air Temperature Alarm Offset, even though heating has been active for at least the Supply Air Temperature Alarm Delay. To resolve this, verify that the heating elements on the rooftop are functioning properly.
  • Z
    zpayneSep 13, 2025
    How to fix Outdoor Temp Fail on Johnson Controls TEC3322-1 Controller?
    • A
      Arthur MarshSep 13, 2025
      If you are experiencing an Outdoor Temp Fail error with your Johnson Controls Controller, it means the external outdoor air temperature sensor is either disconnected or has failed. Here's what you can do: 1. Check the sensor's wiring. 2. If the sensor was intentionally disconnected, reset the sensors through the menu. 3. If the issue continues, you should order replacement units and return the faulty devices to Johnson Controls under the RMA program.
  • B
    Brenda HernandezSep 9, 2025
    Why does the Johnson Controls Fan controller show an error when trying to upgrade the firmware?
    • K
      Kristina PatrickSep 9, 2025
      If the Johnson Controls Fan controller shows an error when trying to upgrade the firmware, it means the firmware on the USB drive is below the minimum required version (Error code 1025). Use firmware version 3.0.2.xxxx (for networked models) or 2.0.2.xxxx (for wireless models) or higher. A reboot is required to clear the Firmware Mismatch fault that occurs.
  • C
    Chase HallSep 14, 2025
    What does it mean when my Johnson Controls Controller displays an Open Window error?
    • J
      Jose LeeSep 15, 2025
      If your Johnson Controls Controller displays an 'Open Window' error, it means the switch connected to the BI configured for Open Window is sensing that a window is open, and control has been shut down. Here's how to resolve it: 1. Close the window to resume control. 2. Check the sensor functionality with an ohmmeter, and verify the wiring to the TEC. 3. If problems persist, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • Y
    younglisaSep 23, 2025
    What does Controller Fault mean on Johnson Controls Controller?
    • J
      James SteeleSep 23, 2025
      If your Johnson Controls Controller displays 'Controller Fault', it means the controller has detected an internal fault that it cannot recover from, or an unknown error has prevented the controller from turning on. The suggested solution is to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • N
    Nicole SmithAug 28, 2025
    What to do if Johnson Controls Thermostat shows Supply Fan Fault?
    • J
      Jeffrey LoganAug 28, 2025
      If your Johnson Controls Thermostat displays 'Supply Fan Fault', it means the Supply Fan Status configured for either BI1 or BI2 has not proved within the configured Fan Alarm Delay. To resolve this: 1. Verify that the Supply Fan is operating when turned on. 2. Verify that the Supply Fan Status wiring is connected correctly.
  • K
    Kevin MendezAug 28, 2025
    What causes Supply Fan Runtime Limit Extended on Johnson Controls Thermostat?
    • R
      Rodney FullerAug 28, 2025
      If your Johnson Controls Thermostat displays 'Supply Fan Runtime Limit Extended,' it means the Supply Fan Runtime has exceeded the configured Supply Fan Runtime Limit. To address this: 1. Service the Supply Fan. 2. Reset the Supply Fan runtime.

Johnson Controls TEC3322-1 Series Specifications

General IconGeneral
Product SeriesTEC3322-1 Series
ManufacturerJohnson Controls
CategoryController
DisplayLCD
Enclosure RatingIP30
TypeElectronic Thermostat
Input Voltage24 VAC
Temperature Range32 to 122 °F
Control ModeOn/Off
MountingWall

Related product manuals