VG1000 Series Forged Brass Ball Valves Installation Instructions
12
Technical Specifications
VG1000 Series Forged Brass Ball Valves (Part 1 of 2 )
Service
1
Hot Water, Chilled Water, 50/50 Glycol Solutions, and
15 psig (103 kPa) Saturated Steam for HVAC Systems
Fluid Temperature Limits Water VG12x1 and VG18x1 Series: 23 to 203F (-5 to 95C)
VG12x5 and VG18x5 Series: -22 to 284F (-30 to 140C)
Steam VG12x1 Series: Not Rated for Steam Service
VG12x5 Series: 15 psig (103 kPa) at 250°F (121°C)
Maximum Fluid Temperature
Limits
212°F (100°C) VA9104
VA9300
VA9203
VA9208
284°F (140°C) VA9104 with M9000-561 Thermal Barrier
VA9300 with M9000-561 Thermal Barrier
VA9203 with M9000-561 Thermal Barrier
VA9208 with M9000-561 Thermal Barrier
Valve Body Pressure/
Temperature Rating
Water VG1241, VG1245, VG1841, and VG1845 Series:
580 psig (4,000 kPa) at 203°F (95°C) (PN40)
464 psig (3,196 kPa) at 284°F (140°C) (PN40)
VG1275 and VG1875 Series:
300 psig (2,067 kPa)
VG1295 and VG1895 Series:
300 psig (2,067 kPa)
Steam 15 psig (103 kPa) Saturated Steam
Maximum Closeoff Pressure 200 psig (1,378 kPa)
Maximum Recommended Operating Pressure
Drop
50 psig (340 kPa)
Flow Characteristics Two-Way Equal Percentage
Three-Way Equal Percentage Flow Characteristics of In-line Port A (Coil) and
Linear Flow Characteristics of Angle Port B (Bypass)
Rangeability
2
Greater than 500:1
Minimum Ambient Operating
Temperature
-4°F (-20°C) VA9104 and M9104 Series Non-Spring Return Actuators
-22°F (-30°C) VA9203 Series Spring Return Actuators
VA9300 Series Non-Spring Return Actuators
-40°F (-40°C) VA9208 Series Spring Return Actuators
Maximum Ambient
Operating Temperature
3
140°F (60°C) VA9104 and VA9300 Series Non-Spring Return Actuators
VA9203 and VA9208 Series Spring Return Actuators
Leakage 0.01% of Maximum Flow per ANSI/FCI 70-2, Class 4
(Two- and Three-Way Control Port)
1% of Maximum Flow for Three-Way Bypass Port
End Connections National Pipe Thread (NPT): 1/2 to 2 in. (DN15 to DN50)
Sweat: 1/2 to 1 in. (DN15 to DN25)
Use a low melting point solder.
Press (ProPress compatible): 1/2 to 1 in. (DN15 to DN25)
Press end connections are designed to work with RIDGID pressing
tools.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls VG1000 Series and is the answer not in the manual?

Johnson Controls VG1000 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelVG1000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals