VMA1400 Series Overview and Engineering Guidelines Technical Bulletin 34
The differential pressure sensor is part of all VMAs (1410, 1420,
1430). The damper actuator is part of the VMA1410/1420. A separate
damper actuator is required for a VMA1430. VMAs cannot share
room sensors.
Dual duct applications require one additional damper actuator and
differential pressure sensor. The actuator M9104-AGS-2N is a
combination of these components.
If VMAs are installed on an N2 Bus connected to an NCM, the NCM
requires a minimum of 4 MB of memory.
2. Coordinate parts ordering and delivery, including:
placing orders through Johnson Controls Customer Service
determining shipping destinations
coordinating VMA manufacturing and delivery issues
coordinating box manufacturer issues
coordinating boxes with VMAs delivered to job
determining status of software, documentation, and
drawings
Note: The VMA can be shipped in individual packages or bulk
shipped (maximum 10 VMAs per box). Separate product codes define
your order preference.