SHOP DRAWING REVIEW
2995 Sidco Drive
Nashville, TN 37204
(615) 383-1113
FAX (615) 386-8469
www.ssr-inc.com
SSR # 11120270
REVIEWER: Rick Wood
DATE: 28Jan2013
PROJECT NAME: Corning Hospital
SECTION NO.: 23 64 16
Review is for general compliance with
SSR LOG NO.:
the design concept of the project and
EQUIPMENT/MATERIAL DESCRIPTION:
general compliance with the information
chillers
given in the contract documents only.
Any action shown is subject to the
requirements of the plans, specifications,
Due to the volume of information in the submittal
and other contract documents.
listed above, this Submittal Review form lists the
comments of the reviewer.
No Exceptions Taken
The submittals have not been marked.
X Make Corrections Noted
A copy of this review must remain with each copy
Amend & Resubmit
of the submittal.
Rejected
NO.
COMMENTS
Condenser and evaporator shells shall have 150 lb flanged pipe connections, not grooved
pipe connections
Note special requirements for CAPACITY TEST penalty for factory performance testing in
specifications- use ARI standard procedures but note additional requirement in specs
No information on head pressure controller, which is the responsibility of the mfr- see specs
and verify compliance/inclusion of scope
No information on refrigerant pumpout system see specs and verify compliance
No information on refrigerant monitor system see specs and verify compliance