“Control panel – Schedule”
If any faults other than those listed above occur during a soft shutdown, the soft shutdown is
aborted, the run signal to the compressor motor starter is de-energized and the compressor or
compressors immediately enter Coastdown.
If an operator initiates a Local Stop with the Keypad Rocker Switch or any fault occurs other than
those listed immediately above, a Fault Shutdown is performed on all running compressors.
Simultaneously, the run signal to the compressor motor starter(s) is de-energized, the
compressor(s) enters Coastdown, and the pre-rotation vanes and discharge valve(s) are driven
closed.
15Model YD Mod D with OptiView Control Center