How to troubleshoot a Johnson Controls York YCSE 040 compressor that does not operate?
- JJoshua KelleyAug 17, 2025
If the Johnson Controls Chiller compressor isn't operating, first check the chilled water pump's interlock circuit to see if it's open. Inspect the pump contactor and repair or replace it if needed. Also, examine the electrical protective devices for any trips and rectify any faults. Finally, verify the wiring connections for the compressor power source and interchange two of the three terminals (R, S, and T) at the main power source terminals if the wiring is incorrect; then reset the "ON" switch.