Installation procedure
Long pipe and high drop
1. Allowable pipe length and height difference
YV2VYH010 type: Maximal length and drop height permissible of refrigerant pipe
YV2VYH015~018 type: Maximal length and drop height permissible of refrigerant pipe
Total length of pipe (actual length)
Total length of pipe (actual length)
Pipe length of indoor unit which is furthest
to the rst branch piping L
(※)
pipe length of indoor unit which is furthest
to the rst branch piping L
(※)
Drop height between indoor units h
Drop height between indoor units h
Drop height between indoor
and outdoor unit H
Drop height between indoor
and outdoor unit H
Longest pipe L
Longest pipe L
Piping lengthPiping length
Drop
height
Drop
height
Actual length
Actual length
50m
100m
35m
15m
30m
30m
30m
20m
20m
10m
10m
70m
Permissible value
Permissible value
pipe in above diagram
pipe in above diagram
L1+L2+L3+L4+a
+b+c+d+e
L1+L2+L3+L4+a
+b+c+d+e
L1+L2+L3+L4+e
L1+L2+L3+L4+e
L2+L3+L4+e
L2+L3+L4+e
Up outdoor
Up outdoor
Under outdoor
Under outdoor

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls YORK YV2VYH015KAS-D-X and is the answer not in the manual?

Johnson Controls YORK YV2VYH015KAS-D-X Specifications

General IconGeneral
BrandJohnson Controls
ModelYORK YV2VYH015KAS-D-X
CategoryAir Conditioner
LanguageEnglish

Related product manuals