15
Refer to Tables 5-2&5-3 for the specifications of the power cord and communication wire. A wiring capacity that is too small will cause the
electrical wiring to become too hot, and lead to accidents when the unit burns and becomes damaged.
Table 5-2
Model
MISTRALSU15---MISTRALSU80
Power
supply
220-240V~50/60Hz
Communication wire between
indoor unit and wired controller *
Shielded 3×AWG16-AWG18
CIRCUIT BREAKER/FUSE(A) 15/15
Phase
Volt and frequency
1-phase
Please refer to the corresponding wired controller manual for the wired
controller wiring.
Select the wire diameters( minimum value) individually for each unit based on the table 5-3.
Maximum allowable voltage range variation between phases is 2%.
Select circuit breaker that having a contact separation in all poles not less than 3 mm providing full disconnectionwhere MFA is used to select
the current circuit breakers and residual current operation breakers:
Table 5-3
Rated current of applianceA
Nominal cross-sectional area (mm )
>3
>6
>10
>16
>25
>32
>50
and
and
and
and
and
and
and
≤3
≤6
≤10
≤16
≤25
≤32
≤50
≤63
0.75
1
1.5
2.5
4
6
10
and
and
and
and
and
and
and
1
1.5
2.5
4
6
10
16
1
1
1.5
2.5
4
6
10
and
1 and
and
and
and
and
and
and
2.5
2.5
2.5
4
6
10
16
25
0.5 and 0.75
Flexible cords
Cable for fixed wiring
2