1 Introduction
6
1.2 Application
Surface-mounting thermostats Series ATH.-SE-.. are approved for monitoring
installations on steel-hulled ocean-going ships (e.g. steam and boiler plant,
indirect heating systems) as:
Temperature monitor (TW)
Safety temperature monitor STW (STB)
Safety temperature limiter (STB).
The versions comply with DIN EN 14597 and are approved as per the guide-
lines of the Classification Societies:
-DNV GL
- Bureau Veritas
- Pressure Equipment Directive 2014/68/EU
(ATH.-SE-20(STW) and ATH.-SE-70(STB) only)
1.3 Marking
H
Surface-mounting thermostats Type ATH.-SE-.. are approved as per DIN EN 60730-
2-9.
1.4 Safety notes
Physical and toxicological properties of substances which may escape in the
event of a system break:
A
Cutting through or kinking the capillary of the surface-mounting thermostats
Type ATH.-SE-.. will lead to permanent failure of the instrument!
H
In the event of a measuring system breakage, the filling liquid can escape.
There is currently no statement by the health authority concerning hazards to
health in the event of short-term exposure and low concentration, e.g. in the
event of a measuring system break.
End of scale Dangerous
reaction
Fire/explosion hazard Water
contami-
nation
Toxicological data
Ignition
temperature
°C
Explosion
limit
% v/v
irritant danger to
health
toxic
below +200 °C no +355 °C 0.6 - 8 yes yes yes no
+200 °C to +300 °C
no +490 °C - - yes yes yes no