3 Modbus protocol description
3.9 Error messages
3.9.1 Modbus error codes
The slave device does not respond
The slave will not respond in the following cases:
The baud rate and/or data format of the master and slave do not match
The used device address does not match the slave address contained in the protocol
The checksum (CRC) is not correct
The instruction from the master is defined incompletely or excessively
The number of words to read is zero
In these cases, the data request should be sent again after a timeout time of approx. 1 s has elapsed.
Error codes
If the data request from the master has been received by the slave without transmission errors but can-
not be processed, the slave responds with an error code. The following error codes may occur:
01 = Invalid function
02 = Invalid address or too many words need to be read or written
08 = Value is write-protected
Response in case of error
The function code is "OR"-linked with 0x80. As a result, the highest value bit (MSB) is set to 1.
Example
The response contains the error code 08 because the address 0x4802 is write-protected.
Slave address Function XX OR 80h Error code Checksum CRC
1 byte 1 byte 1 byte 2 bytes
Data request:
01 06 48 02 00 01 FE 6A
Slave Write word Word address Word value CRC
Response:
01 86 08 43 A6
Slave OR function Error CRC

Other manuals for JUMO diraTRON Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the JUMO diraTRON Series and is the answer not in the manual?

JUMO diraTRON Series Specifications

General IconGeneral
BrandJUMO
ModeldiraTRON Series
CategoryController
LanguageEnglish

Related product manuals