JVA ELECTRIC FENCE SYSTEMS
23
Installation Programming Options
7.6.3 Fence Alarm Voltage (03x#)
This option sets the voltage
threshold below which the fence
alarm will occur. The default
Fence Alarm Voltage is 4 kV in
conventional mode and 3 KV in

this threshold is for both positive
and negative fence wires.
7.6.4 Low Power Alarm Level (05x#)
This option sets the voltage threshold below
which the fence alarm will occur. The default
Fence Alarm Voltage is 500 Volts.
Value (x) Voltage
0 300 Volts
1 500 Volts
2 700 Volts
3 900 Volts
4 1100 Volts
5 3.0%
Low Power Alarm Level (05x#)
7.6.5 Missed Pulse Count (06x#)
This option enables the pulse count to be
varied from the default (3). This is the number
of bad or missing pulses that are counted
before the alarm occurs.
NOTE: The lower this option is set, the more
likely you are to get false alarms.
Value (x) Missed Pulses
0 1
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
Missed Pulse Count (06x#)
Value (x)
Voltage:
Conventional mode
Voltage:
Bi-Polar Mode
0 1.5kV 1.5kV
1 2.0kV 1.8kV
2 2.5kV 2.1kV
3 3.0kV 2.4kV
4 3.5kV 2.7kV
5 4.0kV 3.0kV
6 4.5kV 3.3kV
7 5.0kV 3.6kV
8 5.5kV 3.9kV
9 6.0kV 4.2kV
Fence Alarm Voltage (03x#)