2. Before installing your stove
Jydepejsen stoves Cosmo, Cubic, Trend-linel+2+3, Troja 1+2+3, Soft-line, Fine-line, Zeus,
Athene, Hera and Avanti are tested by OMNI-Test Laboratories, Inc. of Oregon and are listed
to UL 1482-2010 and ULC S627-2000. They are also EPA certified and meet the more
stringent WA State Environmental standards.
If the stove is not installed properly, a home fire may result. To reduce the risk of fire, follow the
installation instructions. Contact local building or fire officials about restrictions and installation
inspection requirements in your area.
It is recommended to install a smoke detector in the room or nearby room where the stove is
being installed as a precautionary measure.
DO NOT INSTALL IN A MOBILE HOME.
Floor plate/floor protection
A floor plate of non-combustible material (tempered glass floor plates are acceptable) must
cover under the stove and extend 16" (41 cm) (18" (45 cm) in Canada) in front of the stove
door, 8" (20 cm) beyond the sides of the fuel-loading door, and under the pipe and 2" (5 cm)
beyond each side for back venting. In Canada, the 8" (20 cm) floor protection is required
beyond the sides of the stove and in the back of the stove (0" in the back for the US).
If the material has an R (Thermal resistance) rating use the designated thickness and no
conversion is needed. R values can be added for multi-layered materials.
If the material has a K (Thermal conductivity) rating convert this to an R rating using the
formula R=1/kxt (t=thickness in inches).
If the material has a C (Thermal conductance) rating convert this to an R rating using the
formula R=1/C.
Floor/ foundation wall
The stove must be installed/hanged on a non-combustible foundation/at a non-combustible
wall - i.e. where a tile or brick floor is non-existing, the stove must meet the demands for the
distance to combustible material under/above/beside the stove, according to applicable
legislative requirements. Consult you dealer before installing the stove.
Wall and corner models
If you have a Cubic Wall/Cubic Corner/Cubic W200 the stove must be installed with the
enclosed furnishings and should meet the NFPA211 guidelines. The installation must not
weaken the chimney construction. The anchoring must be done in consultation with your
dealer/chimney sweep.
Cubic 166/215
The tall models may reach the ceiling (or less than the 18" clearance). If the unit does not meet
the proper clearance to the ceiling, the chimney pipe must be used to connect to the fire box.