Installation, Start-up, Operating and
Service and Maintenance Instructions
NOTE: Read the entire instruction manual before starting the installation.
TABLE OF CONTENTS
REQUIRED NOTICE FOR MASSACHUSETTS
INSTALLATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 1 Minimum Clearances to Combustible Materials for All Units
5
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 2 – Loose Parts Bag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CODES AND STANDARDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCE-
DURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
AIR FOR COMBUSTION AND VENTILATION . . . . . . . . . . . . . . 8
CONDENSATE TRAP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 3 – Minimum Free Area Required for Each Combustion Air
Opening or Duct to Outdoors. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 4 – Minimum Space Volumes for 100% Combustion, Ventila-
tion and Dilution Air from Outdoors . . . . . . . . . . . . . . . . . . . . . . 10
CONDENSATE DRAIN CONNECTION . . . . . . . . . . . . . . . . . . . . 12
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 5 – Opening Dimensions - In. (mm) . . . . . . . . . . . . . . . . . 17
Table 6 – Air Filter Selection and Duct Sizing - In. (mm) . . . . . 19
Table 7 – Filter Media Pressure Drop (Clean) Versus Airflow - In.
W.C. (Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 8 – Filter Media Pressure Drop (Clean) Versus Face Velocity-
In. W.C. (Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 9 Cooling4 and Heating Air Delivery - CFM (Bottom Return5
with Filter) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
GAS PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 10 – Maximum Capacity of Pipe . . . . . . . . . . . . . . . . . . . . 25
ELECTRICAL CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 11 – Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
VENTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 12 – Vent Termination Kit for Direct Vent (2-pipe) Systems33
Table 13 – Approved Combustion-Air and Vent Pipe, Fitting and Ce-
ment Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 14 – Maximum Equivalent Vent Length - Ft. . . . . . . . . . . 42
Table 15 – Deductions from Maximum Equivalent Vent Length - Ft.
(M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 16 – Maximum Allowable Exposed Vent Lengths in Uncondi-
tioned Space Insulation Table - Ft. / M . . . . . . . . . . . . . . . . . . . . 44
Table 17 – Hanger Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
START-UP, ADJUSTMENT, AND SAFETY CHECK . . . . . . . . . 51
Table 18 – Altitude Derate Multiplier for USA. . . . . . . . . . . . . . 54
Table 19 – Blower Off Delay Setup Switch . . . . . . . . . . . . . . . . 56
Table 20 Orifice Size and Manifold Pressure (In. W.C.) for Gas Input
Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Table 21 – Gas Rate (CU ft./hr). . . . . . . . . . . . . . . . . . . . . . . . . . 58
SERVICE AND MAINTENANCE PROCEDURES. . . . . . . . . . . . 58
WINTERIZATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
PARTS REPLACEMENT INFORMATION GUIDE . . . . . . . . . . . 71
MODEL NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Most states in the USA and jurisdictions in Canada have laws that
require the use of Carbon Monoxide (CO) alarms with fuel burning
products. Examples of fuel burning products are furnaces, boilers, space
heaters, generators, water heaters, stoves/ranges, clothes dryers,
fireplaces, incinerators, automobiles, and other internal combustion
engines. Even if there are no laws in your jurisdiction requiring a CO
Alarm, it’s highly recommended that whenever any fuel burning product
is used in or around the home or business that the dwelling be equipped
with a CO Alarm(s). The Consumer Product Safety Commission
recommends the use of CO Alarm(s). The CO Alarm(s) must be
installed, operated, and maintained according to the CO Alarm
manufacturer’s instructions. For more information about Carbon
Monoxide, local laws, or to purchase a CO Alarm online, please visit the
following website. https://www.kidde.com.
A200326
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1E, with permission of National Fire Protection Association, Quincy, MA
02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI
on the referenced subject, which is represented only by the standard in its entirety.
F96VTN and G96VTN
Two-Stage, Non-Communicating, Variable-Speed ECM, Multipoise, Condensing
Gas Furnace
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury and/or
death.
Carbon Monoxide (CO) is a colorless, odorless, and tasteless poisonous
gas that can be fatal when inhaled. Follow all installation, maintenance,
and service instructions. See additional information below regarding
the installation of a CO Alarm.
Use of the AHRI Certified TM Mark indicates
a manufacturer's participation in the program.
For verification of certification for individual
products, go to www.ahridirectory.org .
Question and Answer IconNeed help?

Do you have a question about the KeepRite G96VTN0801716A and is the answer not in the manual?

Summary

Required Notice for Massachusetts

Installations

Requirements for Massachusetts installations.

Location

Air for Combustion and Ventilation

Direct Vent (2-pipe) Applications

Combustion air requirements for direct vent systems.

Combination of Indoor and Outdoor Air

Combining indoor and outdoor air for combustion.

Non-Direct Vent (1-pipe) Applications

Combustion air requirements for non-direct vent systems.

Ventilated Combustion Air Applications (for U.S. Only)

Combustion air for USA ventilated applications.

Outdoor Combustion Air Method

Method for providing outdoor combustion air.

Condensate Trap

Condensate Trap - Upflow Orientation

Condensate trap configuration for upflow orientation.

Condensate Trap - Downflow Orientation.

Condensate trap configuration for downflow orientation.

Condensate Trap - Horizontal Orientation.

Condensate trap configuration for horizontal orientation.

Condensate Drain Connection

Upflow;Downflow Orientation

Condensate drain routing for upflow/downflow.

For Right Side Condensate Drain:

Steps for right-side condensate drain connection.

Left Side Drain Pipe Orientation for Condensate Discharge

Orientation for left-side drain pipe discharge.

For Left Side Condensate Drain Connection:

Steps for left-side condensate drain connection.

Horizontal Orientation

Condensate drain connection for horizontal orientation.

Installation

Upflow Installation

Installation procedure for upflow configuration.

Bottom Return Air Inlet

Instructions for bottom return air inlet.

Horizontal Installation

Installation for horizontal orientation.

Supply Air Connections

Connecting supply air ducts to the furnace.

Side Return Air Inlet

Instructions for side return air inlet.

Return Air Connections

Connecting return air ducts to the furnace.

Downflow Installation

Installation procedure for downflow configuration.

Filter Arrangement

Filter and Return Duct Sizing

Guidance on sizing filters and return ducts.

Air Ducts

Return Duct Sizing

Guidance on sizing return ducts.

Gas Piping

Gas Pipe Grommet

Installing gas pipe grommets for direct vent applications.

Electrical Connections

115-V Wiring

Instructions for 115-V wiring connections.

J-Box Installation

External Electrical Box on Furnace Casing

Instructions for mounting an external electrical box.

For a top panel-mounted external electrical box, complete the following:

Steps for mounting a top-panel external electrical box.

For a side-mounted external electrical box, complete the following:

Steps for mounting a side-external electrical box.

Venting

Locating the Vent Termination

Configure the Furnace

Installing the Vent Pipe Adapter and Combustion Air Pipe Adapter

Installing the Vent Termination

Start-Up, Adjustment, and Safety Check

Prime Condensate Trap with Water

Adjustments

Adjust Manifold Pressure

Service and Maintenance Procedures

General

General service and maintenance responsibilities.

Care and Maintenance

Servicing Hot Surface Igniter

Flushing Collector Box and Drainage System

Cleaning Heat Exchangers

Service

Troubleshooting Guide

Troubleshooting Guide (Continued)

Sequence of Operation

KeepRite G96VTN0801716A Specifications

General IconGeneral
Model NumberG96VTN0801716A
CategoryFurnace
Efficiency Rating96% AFUE
Heating Capacity80, 000 BTU/h
Input BTU80, 000 BTU/h
Output BTU76, 800 BTU/h
StagesTwo-Stage
Blower MotorVariable Speed ECM
Fuel TypeNatural Gas
Ignition TypeHot Surface Ignition
TypeGas
Warranty10-Year Parts Limited Warranty