40 Keysight 34921A-34925A Low Frequency Multiplexer Modules User’s Guide 
Low Frequency Multiplexer Modules 34924A 70-Channel Reed Multiplexer
34924A 70-Channel Reed Multiplexer
The high-density 34924A 70-Channel Reed Multiplexer (70-Ch Reed MUX) is 
divided into two banks with 35 non-latching reed switches (channels 1-35 and 
36-70) in each. This module also contains eight armature Analog Bus relays 
(channels 911-914 and 921-924), four on each bank that can connect the bank 
relays to the system Analog Buses. Through ABus1 and ABus2 you can connect 
any of the channels to the system DMM for voltage or resistance measurements. 
See the simplified schematic on page 42. 
Using program commands or the mainframe front panel, you can control each of 
the channel switches individually, and thus configure the 34924A in any of these 
modes:
- two independent 35-channel 2-wire MUXes. This configuration requires 
neither using external wiring nor connecting through the internal Analog 
Buses. 
- one 70-channel, 2-wire MUX. You must use external wiring or connect 
through the internal Analog Buses for this configuration.
- one 35-channel 4-wire MUX. This configuration requires neither using 
external wiring nor connecting through the internal Analog Buses. For 4-wire 
resistance measurements, the instrument automatically pairs channel n on 
Bank 1 (source) with channel n+35 on Bank 2 (sense) to provide these 
connections. Four-wire controls occur only when doing 4-wire measurement 
operations through the internal DMM, such as MEASure:FRESistance? or 
scanning a channel previously configured as 4-wire. 
In 2-wire mode, you can close no more than 20 channels simultaneously due to 
power dissipation. These 20 channels are split 10 to a bank. However, note that 
Analog Bus relays count half as much as channel relays in that total. For 
example, with one Analog Bus relay closed, you can close up to a maximum of 19 
channel relays. If you try to close more than the allowed number of channels, you 
will receive an error message. 
In all modes, this module has capability to scan as many as 500 channels/second 
using the internal DMM. With the automatic “break-before-make” connection 
operation, you are assured that no two signals are connected to each other 
during a scan. 
Because user-attached reactive loads and backplane 
parasitic capacitance may result in high in-rush currents, 
100 
in-rush resistors protect the reed relays from damage 
and performance degradation. Therefore, you must consider 
these resistors when you are designing a measurement. 
Refer to the simplified schematic on page 42. 
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com