CABLE SPECIFICATION
The DC cables must have a suitable cross-section for their length, according to this table:
Note! The length is from the battery to the refrigerator.
5
Cable Area
12V Max Cable Length* 24V Max Cable Length*
BATTERY PROTECTION VOLTAGES
12V Battery Protection
Voltage Setting
Turn Off Compressor
(to protect battery)
Early warning alarm system
will notify before turning off
compressor (to protect battery)
Turn On
Compressor
Low Level
Medium Level
High Level
10.3V
11.1V
11.6V
10.6V
11.3V
11.9V
11.4V
12.2V
12.7V
24V Battery Protection
Voltage Setting
Turn Off Compressor
(to protect battery)
Early warning alarm system
will notify before turning off
compressor (to protect battery)
Turn On
Compressor
Low Level
Medium Level
High Level
21.5V
23.3V
24.5V
23.6V
24.8V
23.0V
25.3V
26.2V