Architectural and Engineering
Specifications
The smoke alarm shall be Kidde model i12080 or approved equal. It shall be
poweredbya120VAC,60Hzsourcealongwitha9Vbatterybackup.Theunit
shall incorporate an ionization sensor with nominal sensitivity of .50 to .85%/ft.
Thetemperatureoperationrangeshallbebetween40˚Fand100˚F(4˚Cand38˚C)
and the humidity operation range shall be 5% - 95% relative humidity.
The smoke alarm can be installed on any standard single gang electrical box,
uptoa4”octagonjunctionbox.Theelectricalconnection(tothealarm)shallbe
madewithaplug-inconnector.Amaximumof24Kiddedevicescanbeinter-
connected in a multiple station arrangement. The interconnect system must not
exceedtheNFPA(NationalFireProtectionAssociation)limitof18initiatingdevices,
ofwhich12canbesmokealarms.With18initiationdevices(smoke,heat,CO,
etc.), interconnected, it is still possible to interconnect 6 strobe lights and or relay
modules. The unit shall provide optional tamper resistance that deters removal of
the unit from the wall or ceiling.
The alarm shall include a safety light that shall be powered by a 9V alkaline
battery. The safety light shall provide 15 minutes of light when the alarm is
sounding. The alarm shall include a test button that will electronically simulate
the presence of smoke and cause the unit to go into alarm. This sequence tests
theunit’selectronics,batteryandhorntoensureproperoperation.
Theunitshallincludeapiezoelectrichornthatisratedat85dBat10feet.
TheunitshallincludeSmartHush
TM
feature that silences the unit for approximately
7 minutes if a nuisance condition occurs. The unit shall also include a low battery
warningutilizingabriefalarmchirpevery30-40secondsforaminimumof
seven (7) days.
TheunitshallincorporateredandgreenLEDindicators.ThegreenLED(when
illuminated)indicatesthepresenceofACpower.TheredLED(locatedunderthe
TEST/Hushbutton)hasfour modes of operation:
Standby Condition:TheredLEDwillflashevery30-40secondstoindicatethat
the smoke alarm is operating properly. Alarm Condition: When the alarm senses
productsofcombustionandgoesintoalarmtheredLEDwillflashoneflashper
second.TheflashingLEDandpulsatingalarmwillcontinueuntiltheairiscleared.
Whenunitsareinterconnected,onlytheredLEDofthealarmthatsensesthe
smoke or is being tested (the originating unit) will flash. All other units in the
interconnectedsystemwillsoundanalarmbuttheirredLED’swillNOTflash.
Alarm Memory: This smoke alarm is equipped with an alarm memory, which
providesavisualindicationwhenanalarmhasbeenactivated.TheredLEDwill
illuminate for about 1.5 seconds every 16 seconds to indicate the memory
condition. Smart Hush
TM
Mode:TheredLEDwillilluminatefor1.5 seconds every
8seconds,indicatingthesmokealarmisintheSmartHush
TM
Mode.
TheunitshallataminimummeettherequirementsofUL217,NFPA72,(chapter
11),TheStateofCaliforniaFireMarshall,NFPA101(Oneandtwofamilydwellings)
FederalHousingAuthority(FHA),HousingandUrbanDevelopment(HUD).
Itshallalsoincludea10-yearmanufacture’slimitedwarranty.
120V AC/DC Smoke Alarm
Safety Light
Part Number 21006379
Model i12080
Technical Specifications
Model: i12080
UPC: 0-47871-40382-0
PowerSource: 120VAC (
80mA), 60HZ,9Vbatterybackup
Sensor: Ionization
AudioAlarm: 85dBat10ft
TemperatureRange: 40˚F(4.4˚C)to100˚F(37.8˚C)
HumidityRange: 5%-95%relativehumidity(RH)
Size: 5.6”indiameterx1.55”depth
Weight: .5lb
Interconnects: Upto24Kiddedevices
LED: Green,receivingacpower
Red,4modesofoperation
Warranty: 10 year limited
Installation of Smoke Alarm
Thesmokealarmmustbeinstalledtocomplywithalllocalcodeshavingjurisdictionin
yourarea.Allwiringshallbeinaccordancewitharticles210and300.3(B)oftheUS
NationalElectricalCode,ANSI/NFPA70andNFPA72.Themultiplestationintercon-
nect wiring must be in the same raceway as the AC power wiring. In addition the
resistance if the interconnect wiring shall be a maximum of 10 ohms. Make certain all
alarms are wired to a single, continuous (non-switched) powerline, which is not pro-
tected by a ground fault interrupter. A maximum of 1000 ft.of wire can be used in
the interconnect system. Use standard UL listed household wire as required by code.
FUSE OR CIRCUIT BREAKER
BLACK
WHITE
RED
L
N
First
Alarm
Additional
Alarms
5.6” 1.5”
Ordering Information
Ordering Dimensions Case/ Layers/ Skid
Number UPC I2F5 Pack Quantity (w x d x h inches) Weight Skid Skid Weight
N/A 0-47871-40382-0 N/A individual* 5.75x1.5x5.75 0.5lbs N/A N/A N/A
21006379 0-47871-40382-0 100-47871-40382-7 CutCase(6units) 6.5x13.25x6 3lbs 147 7 441lbs
*Not for sale by individual unit
1016 Corporate Park Drive
MebaneNC27302
1-800-880-6788
www.Kidde.com
Distributed by:
P/N: KL-i12080 sheet rev. 01-2009

Other manuals for Kidde I12080

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde I12080 and is the answer not in the manual?

Kidde I12080 Specifications

Power IconPower
power source120VAC, 60Hz, 9V battery backup
audio alarm85dB at 10ft
interconnectsUp to 24 Kidde devices
Operating Environment IconOperating Environment
temperature range40˚F to 100˚F
humidity range5% - 95% relative humidity
Weight and Dimensions IconWeight and Dimensions
size5.6” in diameter x 1.55” depth
weight0.5 lb
dimensions5.75 x 1.5 x 5.75 inches