Chapter 1: Fire geometry and smoke movement in buildings 
10  VM-1 Smoke Management Application Guide 
With any of the methods used for smoke zones, 
pedestrian door opening forces must be considered. The 
pressure differences between barriers are important not 
only in the force to open the door, but also the force 
necessary to overcome the door closer. NFPA 101, the 
Life Safety Code establishes a maximum force of 30 lbf 
(133.35 N) to set a door in motion that is an accepted 
benchmark for designers. Occupants must be able to 
open doors leading to escape routes while the smoke 
control system is in operation. 
Types of systems 
Smoke management utilizing active and passive 
methods in combination to modify smoke movement 
must be engineered into a system that is focused upon 
property or people protection. While passive methods of 
smoke management do exist (see NFPA 204), dynamic 
smoke control systems using mechanical equipment to 
meet design goals dominate. NFPA 92B, Guide for 
Smoke Management Systems in Malls, Atria, and Large 
Areas, provides methodologies for determining smoke 
development in large spaces. NFPA 92A, 
Recommended Practice for Smoke control Systems, is 
used for the design, installation, testing, operation, and 
maintenance of systems for smoke control. 
A VM-1 smoke control system (SCS) when installed and 
programmed in accordance with this design manual and 
the criteria set forth by the smoke control system 
designer will help to: 
•  Provide a tenable environment in evacuation routes 
during the time necessary to evacuate people from 
the area 
•  Restrict the movement of smoke from the fire area 
•  Assist in protecting life and property 
•  Maintain tenable conditions in nonfire areas that will 
enable fire personnel to conduct search and rescue 
operations in addition to attacking the seat of the fire 
A VM-1 SCS should be designed, installed, and 
maintained such that the system will remain effective 
during evacuation of the protected areas. Other 
considerations determined by the smoke control system 
designer may dictate that a system should remain 
effective for longer periods. Areas to evaluate in 
determining VM-1 SCS integrity are: 
•  Reliability of power sources 
•  Arrangement of power distribution 
•  Location, and methods of protection for VM-1 
system panels 
•  Building occupancy type 
The design, installation, testing, operation, and 
maintenance of new and retrofitted mechanical air 
conditioning and ventilation systems for the control of 
smoke will require the involvement of several 
interdependent disciplines or parties:  
System designer. Building equipment and controls are 
the responsibility of the system designer. The system 
designer: 
•  Determines the type of smoke control system to be 
used 
•  Defines the size of the expected or design fire 
•  Performs tenability calculations 
•  Establishes and defines smoke zones based on 
building barriers and determines the sizing of fans 
and location of dampers 
The system designer may be an architect, engineer, or 
fire protection professional knowledgeable in the theory 
and application of smoke management and control. The 
system designer creates a specification used by the  
VM-1 SCS designer to create the smoke control system. 
The specification defines how the total system must 
operate under fire or smoke conditions. 
VM-1 SCS designer. Smoke control system operation is 
the responsibility of the VM-1 fire alarm and smoke 
control system designer. The specifications for operation 
of a smoke control system define the methods of 
fire/smoke detection for a particular area and the 
resulting outputs for smoke removal or control functions 
that must take place. Control functions performed by a 
VM-1 panel include the startup and shutdown of HVAC 
or exhaust fans, smoke damper closure, and door 
closure.  
Authority having jurisdiction (AHJ). The AHJ, typically a 
fire official, is important in the determination of firefighter 
control station locations and final acceptance and testing 
of the smoke control system. Involvement of the AHJ 
early in a project helps to ensure that the system 
requirements (typically NFPA 92A) will be met by the 
total system design. The AHJ can establish clear